3-11
IM 05P07A01-01EN
Description of RS-485 Communication (for UT
Advanced with RS-485 Communication)
3
03 Reading multiple D registers
Function
The content of D registers is read continuously for the specified number of registers from
the specified D register No.
• The maximum number of registers that can be read at a time is 100.
• For details on the response format at an error, see “
● Response in an error state
” in
“3.1.3 Configuration of Responses (response from UTAdvanced).”
Message (during normal operation)
Element
Message
start mark
(:)
Address No.
(ADS)
Function code
(0x03)
Register
start No.
Number
of read
registers
Error
check
Message
end mark
(CR+LF)
Number of bytes in RTU mode
None
1
1
2
2
2
None
Number of bytes in ASCII
mode
1
2
2
4
4
2
2
Response (during normal operation)
Element
Message
start mark
(:)
Address No.
(ADRS)
Function code
(0x03)
Byte count
(Note 1)
Register
content
• • •
Number of bytes in RTU mode
None
1
1
1
2
• • •
Number of bytes in ASCII
mode
1
2
2
2
4
• • •
Continuation of response
Register
content
Error
check
Message
end mark
(CR+LF)
2
2
None
4
2
2
Note 1: Byte count = 2 x number of read registers
3.1 Modbus Communication
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...