6-176
IM 05P07A01-01EN
6.6 GREEN Series Compatible D Registers
D0302 to D0480: A1_L1_1 to A4_L1_8 (Loop-1 Alarm-1 setpoint to Alarm-8
setpoint of Groups 1 to 4) (For UT500 Series)
When the Loop-1 Alarm-1 setpoint to Alarm-4 setpoint (D0915: AL1.1, D0916: AL2.1,
D0917: AL3.1, D0918: AL4.1) are the following values (Deviation low limit alarm), the
sign of the alarm setpoint is reversed and is set to UTAdvanced.
AL1.1, AL2.1, AL3.1, AL4.1 = 4, 6, 14, 16, 34, 36, 44, 46
4: Deviation low limit (energized, no stand-by action)
6:
Deviation low limit (de-energized, no stand-by action)
14:
Deviation low limit (energized, with stand-by action)
16:
Deviation low limit (de-energized, with stand-by action)
34: Deviation low limit for target setpoint
(energized, no stand-by action) *
36: Deviation low limit for target setpoint (
de-energized
, no stand-by action) *
44: Deviation low limit for target setpoint
(energized, with stand-by action) *
46: Deviation low limit for target setpoint (
de-energized
, with stand-by action) *
*: For UT551 only
(If the setting value is other than the above, the alarm setpoint is not changed.)
Loop-1 Alarm-1 setpoint to Alarm-8 setpoint of Groups 1
When D0915 (AL1.1) = 4, 6, 14, 16, 34, 44, 36, 46
Symbol
Event
GREEN Series
UTAdvanced
D0302
1.A1
A1_L1_1 (D2504)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A1=10 → 1.A1=-10)
D0327
2.A1
A1_L1_2 (D2524)
D0352
3.A1
A1_L1_3 (D2544)
D0377
4.A1
A1_L1_4 (D2564)
D0402
5.A1
A1_L1_5 (D2584)
D0427
6.A1
A1_L1_6 (D2604)
D0452
7.A1
A1_L1_7 (D2624)
D0477
8.A1
A1_L1_8 (D2644)
Loop-1 Alarm-1 setpoint to Alarm-8 setpoint of Groups 2
When D0916 (AL2.1) = 4, 6, 14, 16, 34, 44, 36, 46
Symbol
Event
GREEN Series
UTAdvanced
D0303
1.A2
A2_L1_1 (D2505)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A2=10 → 1.A2=-10)
D0328
2.A2
A2_L1_2 (D2525)
D0353
3.A2
A2_L1_3 (D2545)
D0378
4.A2
A2_L1_4 (D2565)
D0403
5.A2
A2_L1_5 (D2585)
D0428
6.A2
A2_L1_6 (D2605)
D0453
7.A2
A2_L1_7 (D2625)
D0478
8.A2
A2_L1_8 (D2645)
Loop-1 Alarm-1 setpoint to Alarm-8 setpoint of Groups 3
When D0917 (AL3.1) = 4, 6, 14, 16, 34, 44, 36, 46
Symbol
Event
GREEN Series
UTAdvanced
D0304
1.A3
A3_L1_1 (D2506)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A3=10 → 1.A3=-10)
D0329
2.A3
A3_L1_2 (D2526)
D0354
3.A3
A3_L1_3 (D2546)
D0379
4.A3
A3_L1_4 (D2566)
D0404
5.A3
A3_L1_5 (D2586)
D0429
6.A3
A3_L1_6 (D2606)
D0454
7.A3
A3_L1_7 (D2626)
D0479
8.A3
A3_L1_8 (D2646)
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...