IM 05C01F12-41E

28

 PV Event Function List

PV event is the function to output the PV or deviation alarm related to the created program.

Hysteresis

Temperature setpoint

Deviation setting

Measured value

Opn (on)

Cls (off)

Hysteresis

Hysteresis

Hysteresis

Hysteresis

Temperature setpoint

Temperature setpoint

Deviation setting

Measured value

Cls 
(on)

Opn
(off)

Cls

(on)

Hysteresis

Alarm setting

Measured value

Opn (off)

Opn (off)

Cls (on)

Hysteresis

Alarm setting

Measured value

Opn (off)

Cls (on)

7

6

De-energized 

on deviation 

low limit

1

PV

high limit

No alarm

Deviation 

high and 

low limits

2

PV

low limit

8

Deviation 

within 

high and 

low limits

3

Deviation 

high limit

9

De-energized 

on PV

high limit

4

Deviation 

low limit

10

De-energized 

on PV

low limit

5

De-energized 

on deviation 

high limit

OFF

Measured value

Opn (off)

Opn (off)

Cls (on)

Deviation setting

Hysteresis

Cls (on)

Measured value

Temperature setpoint

Deviation setting

Cls (on)

Hysteresis

Opn (off)

Measured value

Temperature setpoint

Deviation setting

Hysteresis

Opn (on)

Cls

(off)

Alarm setting

Measured value

Hysteresis

Cls (off)

Opn (on)

Alarm setting

Measured value

Measured value

Temperature setpoint

Hysteresis

Deviation setting

Opn (on)

Cls (off)

PV event

(alarm)

type

PV event

(alarm)

type

PV event

type code

Closed

contact

during

PV event

(alarm)

Open

contact

during

PV event

(alarm)

Action

PV event

type code

Closed

contact

during

PV event

(alarm)

Open

contact

during

PV event

(alarm)

“Opn” and “Cls” indicate that 

the relay contact is opened 

and closed; “(on)” and “(off)” 

indicate that the lamp is on 

and off; and white triangles 

indicate temperature control 

setpoints.

Action

“Opn” and “Cls” indicate that 

the relay contact is opened 

and closed; “(on)” and “(off)” 

indicate that the lamp is on 

and off; and white triangles 

indicate temperature control 

setpoints.

Содержание UP150

Страница 1: ...User s Manual Model UP150 Program Temperature Controller IM 05C01F12 41E IM 05C01F12 41E 2001 2 1st Edition...

Страница 2: ...supplied along with the product shipped Therefore both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01F12 41E 1...

Страница 3: ...unting bracket User s manual 1 1 1 Model Model and Suffix Codes Suffix code Description UP150 Program Temperature Controller R V A Relay output time proportional PID or on off control Voltage pulse ou...

Страница 4: ...th of personnel and or damage to the product In the manual the symbol is accompanied by an explanation of the special care that is required to avoid shock or other dangers that may result in injury or...

Страница 5: ...1 second in operating display stops resets the program operation Changes the program setpoints SP and the parameter setpoints Pressing this key increases the parameter setpoint Holding down the key wi...

Страница 6: ...adiation Never place the controller directly on flammable items If the controller has to be installed close to flammable items or equipment be sure to enclose the controller in shielding panels positi...

Страница 7: ...he following figures is chosen for any of the controller max 61 Panel thickness max 47 8 max 44 8 max 44 8 100 12 1 to 10 Unit mm 1 General Mounting min 70 min 70 45 0 6 0 45 0 6 0 25 25 N 1 48 45 0 6...

Страница 8: ...For thermocouple input use shielded compensating lead wires For RTD input use shielded wires which have low resistance and no resistance difference between the 3 wires See the table given later for th...

Страница 9: ...terminals with an insulating sleeve as shown below Power supply and relay contact output 600V vinyl insulated wire cable JIS C3307 0 9 to 2 0mm2 Shielded wire 3 wire UL2482 Hitachi cable Thermocouple...

Страница 10: ...ue PV Input When RET is specified PV Retransmission Output 1 2 4 to 20 mA DC 4 to 20 mA Output Voltage Pulse Output Control Output Specify one for the output signal type 14 15 14 15 Relay Contact Outp...

Страница 11: ...e Upward incline of up to 30 degrees downward incline is not allowed Altitude 2000m or less above sea level Maximum Effects from Operating Conditions 1 Temperature effects Thermocouple DC mV and DC V...

Страница 12: ...mounted on the panel so as not to accidentally touch the terminals when power is being applied 1 You can move between the parameters in each parameter setting display using the key 2 To change the par...

Страница 13: ...CTL parameter In this example PID control mode is selected Step 4 When On off control mode is required press the key to change control mode to On off Changing Control Mode CTL The period flashes Step...

Страница 14: ...Key Key is displayed Yes No Power ON A Operating Parameter Setting Display Setup Parameter Setting Display HOLD ADV CTL HYS Displayed for time proportional PID control CT Displayed when I OFF MR Displ...

Страница 15: ...2 EV1 EV2 SSP STC SP1 TM1 SP2 TM2 SP3 TM3 SP4 TM4 SP5 TM5 SP6 TM6 JC WTZ SP7 TM7 SP8 TM8 SP9 TM9 SP10 TM10 SP11 TM11 SP12 TM12 SP13 TM13 SP14 TM14 SP15 TM15 SP16 TM16 segment 7 segment 8 segment 9 seg...

Страница 16: ...measured input range scale span 0 of measured input range scale span LOC Key lock 0 1 Operating Parameters HOLD Program hold OFF 0 OFF 0 Not execute advance ON 1 Execute advance Displayed when a prog...

Страница 17: ...ge and unit Default User setting Decimal point position of measured input 0 No decimal place nnnn 1 One decimal place nnn n 2 Two decimal places nn nn 3 Three decimal places n nnn 1 Maximum value of m...

Страница 18: ...ut range scale to Max value of measued input range scale Deviation alarm 100 to 100 of measured input range scale span Unit C F 0 PV event 1 Time event Max value of measured input range scale PV alarm...

Страница 19: ...ONF you can set a hysteresis around the on off point SP to prevent chattering On off point Program SP Hysteresis ON OFF The cycle time is the period of on off repetitions of a relay or voltage pulse o...

Страница 20: ...EON1 EOF1 AL1 A1 HY1 EON2 EOF2 AL2 A2 HY2 0 30 1 20 1 PV high limit 110 C 10 C Time event 1 EV1 1 PV event 1 EV1 0 Time event 2 EV2 1 PV event 2 EV2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 50 C 50 C...

Страница 21: ...1 EON2 EOF2 AL2 A2 HY2 Time event 1 EV1 1 PV event 1 EV1 0 Time event 2 EV2 1 PV event 2 EV2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 100 RH Maximum value of measured input range scale Minimum value o...

Страница 22: ...nge the value of parameters Use key to register the setpoint When creating program is finished press the key for at least 3 seconds to return to the operating display The period flashes during change...

Страница 23: ...Press the key for at least 1 second RUN lamp goes out and resets stops the program operation Step 1 Confirm that the controller is in program operation RUN lamp goes out RUN lamp is lit Note Program o...

Страница 24: ...the setpoint of the TMU Time Unit of Program setup parameter to 1 Creating programs by setting target setpoint and segment time As shown in the figure below this method creates programs by setting a s...

Страница 25: ...2 Letting the controller start from the current PV and run according to time settings defined for segment 1 Controller Settings Set the STC Start Code program parameter to 2 Segment 1 Segment 2 Segmen...

Страница 26: ...s from any of the points A SSP to C For other information see the following table Program pattern PV 1 2 3 4 5 C B A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time Example Where Segment 2 is a Soak Segment Th...

Страница 27: ...xample Where Segment 3 is a Soak Segment PV 1 2 3 4 5 C D E B A SSP Seg 1 Seg 2 Seg 4 Seg 3 Time Example With No Soak Segment The starting point of program operation is determined by where the measure...

Страница 28: ...elow B A SSP Seg 1 Seg 2 Time Example Where the Segment Consists of an Ascending Gradient Ramp Only The starting point of program operation is determined by where the measured input value PV is locate...

Страница 29: ...A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time PV 1 2 3 4 5 C D B A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time The starting point of program operation is determined by where the measured input value PV is locat...

Страница 30: ...asured value Opn off Opn off Cls on Deviation setting Hysteresis Cls on Measured value Temperature setpoint Deviation setting Cls on Hysteresis Opn off Measured value Temperature setpoint Deviation se...

Страница 31: ...SEG2 SEG1 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Time event 1 ON time OFF time Time event 2 TM4 TM5 NOTE 1 When you don t want event OFF at the end of program operation set OFF to time event 1 or 2 off t...

Страница 32: ...PV input is tracked Wait operation is available only at a segment junction that transfers from ramp to soak Wait Zone WTZ Wait Zone WTZ Time event SEGn 1 SEGn SEGn 1 The controller UP150 can move to...

Страница 33: ...operation is held time event and segment time are extended only by amount of the hold 1 Hold in soak segment TM1 TM2 TM3 Time ON time OFF time SEG1 PV SEG2 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Hold sec...

Страница 34: ...e SEG1 PV SEG2 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Time event 1 The time when Advance is executed the remaining time of this segment SEG2 is canceled The program moves to the start point of next segmen...

Страница 35: ...nceled by key operation or external contact input digital input When hold status is canceled control output becomes 0 or OFF and event status is OFF 3 Repeat JC 2 At the program termination the contro...

Страница 36: ...all the parameters and set them at their proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and scale setting...

Страница 37: ...ction Taipei TAIWAN Phone 866 2 321 1113 Facsimile 866 2 322 5593 YOKOGAWA AUSTRALIA PTY LTD Private mail bag 24 Centre Court D3 25 27 Paul Street North North Ryde N S W 2113 AUSTRALIA Phone 61 2 9805...

Отзывы: