IM 05C01F12-41E
33
■
Junction Code
The operation at the end of program pattern can be specified by junction code (JC).
(1)
Reset termination (JC = 0)
At program termination, the controller enters reset status. At this time, control output becomes 0% or
OFF, and event status is OFF.
(2)
Hold termination (JC = 1)
At program termination, the system enters hold status. At this time, control output and time event status
are held (PV events do not stop at this time). The hold status continues until canceled by key operation
or external contact input (digital input). When hold status is canceled, control output becomes 0% or
OFF, and event status is OFF.
(3)
Repeat (JC = 2)
At the program termination, the controller repeats execution of same program pattern. At th start of
program operation, PV starts up with gradient-priority. At the start of second time or later where the
repeat action is activated, the program operation always starts from “SSP” regardless of PV.
TM1
TM2
TM3
TM4
TM2
ON time
OFF time
TM3
TM4
Time
TM1
SEG1
PV
SEG2
SEG3
SEG4
SEG2
SEG3
SEG4
SEG1
PV
SP1
SP2
SP3
SP4
SP1
SP2
SP3
SP4
SSP
SSP
PV startup with gradient-priority
When “repeat”, always starts from “SSP”
Time event