IM 05C01F12-41E
10
7.
KEY OPERATIONS
●
UP150 Measured Input Ranges
For example, to select
thermocouple type J (
°
F),
set the range code to 35.
OFF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Thermocouple
RTD
DC voltage
K
J
T
E
R
S
B
N
L
U
Platinel 2
Pt100
JPt100
0 to 100mV
0 to 5V
1 to 5V
0 to 10V
– 270 to 1370
°
C
0.0 to 600.0
°
C
0.0 to 400.0
°
C
– 199.9 to 200.0
°
C
– 199.9 to 999.9
°
C
– 199.9 to 400.0
°
C
– 199.9 to 999.9
°
C
0 to 1700
°
C
0 to 1700
°
C
0 to 1800
°
C
– 200 to 1300
°
C
– 199.9 to 900.0
°
C
– 199.9 to 400.0
°
C
0 to 1390
°
C
– 199.9 to 850.0
°
C
0.0 to 400.0
°
C
– 199.9 to 200.0
°
C
– 19.9 to 99.9
°
C
– 199.9 to 500.0
°
C
– 300 to 2500
°
F
32.0 to 999.9
°
F
32.0 to 750.0
°
F
– 300 to 400
°
F
– 300 to 2100
°
F
– 300 to 750
°
F
– 300 to 1800
°
F
32 to 3100
°
F
32 to 3100
°
F
32 to 3200
°
F
– 300 to 2400
°
F
– 300 to 1600
°
F
– 300 to 750
°
F
32 to 2500
°
F
– 199.9 to 999.9
°
F
32.0 to 750.0
°
F
– 300 to 400
°
F
– 199.9 to 999.9
°
F
0.0 to 100.0
0.000 to 5.000
1.000 to 5.000
0.00 to 10.00
User-scalable
Input type
Range
(
°
C
)
Range
(
°
F
)
Range code
(
°
C
)
Range code
(
°
F
)
EV
RUN
Unspecified
To prevent electric shock, the controller should be mounted on the panel so as not to accidentally touch the
terminals when power is being applied.
(1) You can move between the parameters in each parameter setting display using the
key.
(2) To change the parameter setpoint,
( i ) Change the display value with the
or
key (the period flashes).
(ii) Press the
key to register the setpoint.
(3) In the operating display 1 , 2 or 3 , pressing the
key for at least 3 seconds retrieves the operating parameter setting
display.
(4) In the operating parameter setting display, pressing the
key for at least 3 seconds transfers back to the
operating display 1 .
Registering the parameter PRG to “1” retrieves the program parameter setting display.
Registering the key-lock parameter LOC to “–1” retrieves the setup parameter setting display.
(5) In the setup parameter setting display, pressing the
key for at least 3 seconds transfers back to the operating display 1 .
(6) In the program parameter settting display, pressing the
key for at least 3 seconds transfers back to the
operating display 1 .
At power-on, the program temperature controller displays the operating display 1 , but if the measured
input type setting remains OFF, “IN” appears. In this case, press the
key to display the measured input
range code you want to use, then press the
key to register it. (Refer to the flowchart on page 12 and
13.)