Parameter

Function

Parameter

Function

Control mode

CTL

UP150 has two control mode.
Select one from the following:
a. PID control (PID)
b. On/off control (ONF)

Manual reset

MR

You can set this parameter only for control 
without an integral action (when registered as 
CTL=PID and I=OFF). The controller outputs the 
manual reset (MR) value when PV=SP. For 
example, if you set MR=50%, the controller 
outputs (OUT) 50% when PV=SP.

Hysteresis for 
PV evnets 1 and 2 

HY1,  
HY2

The PV events are output as relay outputs. Since a 
relay has a limited service life, excessive on/off 
actions will shorten the life of a relay. To prevent 
this, you can set a hysteresis band for both PV 
evnets 1 and 2 to moderate excessive on/off 
actions .

DI-function 
selection

DIS

•  When DIS=ON, Mode can be switched by only 

external contact input signal.

•  In order to switch the Mode by key operation, 

OFF must be set at DIS.

Note: UP150 can be switched into “RESET” 

mode by key operation even if DIS=ON.

SUPER  
function   
selection  

SC

The SUPER function is effective in the following cases:
a. An overshoot must be suppressed.
b. The rise-up time needs to be shortened.
c. The load often varies.
Note 1: The SUPER function will not work when 

on/off control is selected, or I or D 
constants is set at OFF in PID control.

Note 2: For some types of systems, the SUPER 

function may not be so useful.  If this is 
the case, turn off the function.

Time event n*
on time
n*=1 or 2  

EON1
EON2

Time event n*
off time
n*=1 or 2  

EOF1
EOF2

The time event feature begins countdown when a 
program starts running, and after the elapse of a 
preset time, output an on-time event signal 
(contact output ON) or off-time event signal 
(contact output OFF).

Hysteresis for 
on/off control 

HYS

For on/off control (CTL=ONF), you can set a 
hysteresis around the on/off point (SP) to prevent 
chattering.

On/off point (Program SP)

Hysteresis

ON

OFF

The cycle time is the period of on/off repetitions of 
a relay or voltage pulse output in time proportional 
PID control. The ratio of the ON time to the cycle 
time is proportional to the control output value.

Cycle time

t ON

t OFF

Control output 
cycle time

CT

PV input bias

BS

This function adds a bias value to the measured 
input value, and the result is used for display and 
control computation.

This function is useful for carrying out fine 
adjustment when the PV value is within the 
required accuracy but it differs from the value 
obtained by other equipment.

PV value inside the controller

measured input value

PV input bias

+

=

ON : HOLD , OFF : Cancel HOLD

COM

3

4

5

ON : RUN , OFF : RESET

SEG1

SEG2

SEG3 SEG4 SEG5

Time

Program
pattern

Time
event

ON time

OFF time

Time Event Diagram

2-seconds filter

Input

10-seconds filter

PV input filter

FL

This function should be used when the PV display 
value may fluctuate greatly, for example, when the 
measured input signal contains noise. The filter is 
of the first-order lag type, and FL sets the time 
constant. If a larger time constant is set, the filter 
can remove more noise.

Maximum/minimum 
value of measured 
input scale

RH, 
RL

Decimal point 
of measured
input

DP

For DC voltage input, the input signal can be scaled for the 
particular engineering unit. For example, if you set the input 
type (IN) at range code 22, the initial range is 0.0 to 100.0.
a. Using DP, set the decimal point position fit for the 

engineering unit you want to use. (In the example below, 
the 2 digits to the right of the decimal point)

b. Next, register the scale values of the measured input scale using 

RH and RL. (In the example below, RH=10.00 and RL=0.00)

Initial scale

100.0 (5V)

0.0 (1V)

10.00 (RH)

0.00 (RL)

Measured input scale 

(after being scaled)

Register the decimal point position using DP.

 Description of Parameters

Содержание UP150

Страница 1: ...User s Manual Model UP150 Program Temperature Controller IM 05C01F12 41E IM 05C01F12 41E 2001 2 1st Edition...

Страница 2: ...supplied along with the product shipped Therefore both manuals have the same contents except for some minor differences in the cross referenced page numbers Revision Record Manual No IM 05C01F12 41E 1...

Страница 3: ...unting bracket User s manual 1 1 1 Model Model and Suffix Codes Suffix code Description UP150 Program Temperature Controller R V A Relay output time proportional PID or on off control Voltage pulse ou...

Страница 4: ...th of personnel and or damage to the product In the manual the symbol is accompanied by an explanation of the special care that is required to avoid shock or other dangers that may result in injury or...

Страница 5: ...1 second in operating display stops resets the program operation Changes the program setpoints SP and the parameter setpoints Pressing this key increases the parameter setpoint Holding down the key wi...

Страница 6: ...adiation Never place the controller directly on flammable items If the controller has to be installed close to flammable items or equipment be sure to enclose the controller in shielding panels positi...

Страница 7: ...he following figures is chosen for any of the controller max 61 Panel thickness max 47 8 max 44 8 max 44 8 100 12 1 to 10 Unit mm 1 General Mounting min 70 min 70 45 0 6 0 45 0 6 0 25 25 N 1 48 45 0 6...

Страница 8: ...For thermocouple input use shielded compensating lead wires For RTD input use shielded wires which have low resistance and no resistance difference between the 3 wires See the table given later for th...

Страница 9: ...terminals with an insulating sleeve as shown below Power supply and relay contact output 600V vinyl insulated wire cable JIS C3307 0 9 to 2 0mm2 Shielded wire 3 wire UL2482 Hitachi cable Thermocouple...

Страница 10: ...ue PV Input When RET is specified PV Retransmission Output 1 2 4 to 20 mA DC 4 to 20 mA Output Voltage Pulse Output Control Output Specify one for the output signal type 14 15 14 15 Relay Contact Outp...

Страница 11: ...e Upward incline of up to 30 degrees downward incline is not allowed Altitude 2000m or less above sea level Maximum Effects from Operating Conditions 1 Temperature effects Thermocouple DC mV and DC V...

Страница 12: ...mounted on the panel so as not to accidentally touch the terminals when power is being applied 1 You can move between the parameters in each parameter setting display using the key 2 To change the par...

Страница 13: ...CTL parameter In this example PID control mode is selected Step 4 When On off control mode is required press the key to change control mode to On off Changing Control Mode CTL The period flashes Step...

Страница 14: ...Key Key is displayed Yes No Power ON A Operating Parameter Setting Display Setup Parameter Setting Display HOLD ADV CTL HYS Displayed for time proportional PID control CT Displayed when I OFF MR Displ...

Страница 15: ...2 EV1 EV2 SSP STC SP1 TM1 SP2 TM2 SP3 TM3 SP4 TM4 SP5 TM5 SP6 TM6 JC WTZ SP7 TM7 SP8 TM8 SP9 TM9 SP10 TM10 SP11 TM11 SP12 TM12 SP13 TM13 SP14 TM14 SP15 TM15 SP16 TM16 segment 7 segment 8 segment 9 seg...

Страница 16: ...measured input range scale span 0 of measured input range scale span LOC Key lock 0 1 Operating Parameters HOLD Program hold OFF 0 OFF 0 Not execute advance ON 1 Execute advance Displayed when a prog...

Страница 17: ...ge and unit Default User setting Decimal point position of measured input 0 No decimal place nnnn 1 One decimal place nnn n 2 Two decimal places nn nn 3 Three decimal places n nnn 1 Maximum value of m...

Страница 18: ...ut range scale to Max value of measued input range scale Deviation alarm 100 to 100 of measured input range scale span Unit C F 0 PV event 1 Time event Max value of measured input range scale PV alarm...

Страница 19: ...ONF you can set a hysteresis around the on off point SP to prevent chattering On off point Program SP Hysteresis ON OFF The cycle time is the period of on off repetitions of a relay or voltage pulse o...

Страница 20: ...EON1 EOF1 AL1 A1 HY1 EON2 EOF2 AL2 A2 HY2 0 30 1 20 1 PV high limit 110 C 10 C Time event 1 EV1 1 PV event 1 EV1 0 Time event 2 EV2 1 PV event 2 EV2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 50 C 50 C...

Страница 21: ...1 EON2 EOF2 AL2 A2 HY2 Time event 1 EV1 1 PV event 1 EV1 0 Time event 2 EV2 1 PV event 2 EV2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 100 RH Maximum value of measured input range scale Minimum value o...

Страница 22: ...nge the value of parameters Use key to register the setpoint When creating program is finished press the key for at least 3 seconds to return to the operating display The period flashes during change...

Страница 23: ...Press the key for at least 1 second RUN lamp goes out and resets stops the program operation Step 1 Confirm that the controller is in program operation RUN lamp goes out RUN lamp is lit Note Program o...

Страница 24: ...the setpoint of the TMU Time Unit of Program setup parameter to 1 Creating programs by setting target setpoint and segment time As shown in the figure below this method creates programs by setting a s...

Страница 25: ...2 Letting the controller start from the current PV and run according to time settings defined for segment 1 Controller Settings Set the STC Start Code program parameter to 2 Segment 1 Segment 2 Segmen...

Страница 26: ...s from any of the points A SSP to C For other information see the following table Program pattern PV 1 2 3 4 5 C B A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time Example Where Segment 2 is a Soak Segment Th...

Страница 27: ...xample Where Segment 3 is a Soak Segment PV 1 2 3 4 5 C D E B A SSP Seg 1 Seg 2 Seg 4 Seg 3 Time Example With No Soak Segment The starting point of program operation is determined by where the measure...

Страница 28: ...elow B A SSP Seg 1 Seg 2 Time Example Where the Segment Consists of an Ascending Gradient Ramp Only The starting point of program operation is determined by where the measured input value PV is locate...

Страница 29: ...A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time PV 1 2 3 4 5 C D B A SSP Seg 1 Seg 2 Seg 4 Seg 5 Seg 3 Time The starting point of program operation is determined by where the measured input value PV is locat...

Страница 30: ...asured value Opn off Opn off Cls on Deviation setting Hysteresis Cls on Measured value Temperature setpoint Deviation setting Cls on Hysteresis Opn off Measured value Temperature setpoint Deviation se...

Страница 31: ...SEG2 SEG1 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Time event 1 ON time OFF time Time event 2 TM4 TM5 NOTE 1 When you don t want event OFF at the end of program operation set OFF to time event 1 or 2 off t...

Страница 32: ...PV input is tracked Wait operation is available only at a segment junction that transfers from ramp to soak Wait Zone WTZ Wait Zone WTZ Time event SEGn 1 SEGn SEGn 1 The controller UP150 can move to...

Страница 33: ...operation is held time event and segment time are extended only by amount of the hold 1 Hold in soak segment TM1 TM2 TM3 Time ON time OFF time SEG1 PV SEG2 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Hold sec...

Страница 34: ...e SEG1 PV SEG2 SEG3 SEG4 SEG5 SP1 SP2 SP3 SP4 SP5 Time event 1 The time when Advance is executed the remaining time of this segment SEG2 is canceled The program moves to the start point of next segmen...

Страница 35: ...nceled by key operation or external contact input digital input When hold status is canceled control output becomes 0 or OFF and event status is OFF 3 Repeat JC 2 At the program termination the contro...

Страница 36: ...all the parameters and set them at their proper values B o Input burnout Check the sensor wiring and correct it OOO PV over scale PV exceeds its effective range Check the input type and scale setting...

Страница 37: ...ction Taipei TAIWAN Phone 866 2 321 1113 Facsimile 866 2 322 5593 YOKOGAWA AUSTRALIA PTY LTD Private mail bag 24 Centre Court D3 25 27 Paul Street North North Ryde N S W 2113 AUSTRALIA Phone 61 2 9805...

Отзывы: