IM 05C01F12-41E
8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
EV2
EV1
COM
PV or Time Event Outputs
11
12
13
External Contact Inputs
3
4
5
RUN
HOLD
HOLD program when DI=ON.
Cancel HOLD program when DI=OFF.
Starts program (RUN) when DI=ON.
Resets program (RESET) when DI=OFF.
COM
When “/EX” is specified.
Can be used when DIS parameter is ON.
RS-485
3
4
5
RSB(+)
RSA(–)
SG
When “/RS” is specified.
CAUTION
To prevent damage to the controller,
never provide 100-240V AC power supply
for power supply AC/DC 24V model (when
⬙
/V24
⬙
is specified).
NOTE
The and stand for the polarity
for DC 24V power supply.
+
–
TC Input
RTD Input
7
8
6
7
8
+
–
B
b
A
Universal input-selectable
input type
DC mV or V Input
7
8
+
–
Measured Value (PV) Input
When “/RET”
is specified.
PV Retransmission Output
+
–
1
2
4 to 20 mA DC
4 to 20 mA Output
Voltage Pulse Output
Control Output
Specify one for the output signal type.
14
15
+
–
14
15
+
–
Relay Contact Output
14
15
NO
COM
(model UP150-RN)
(model UP150-AN)
(model UP150-VN)
Power Supply
9
L
N
10
100-240V AC
9
10
AC/DC 24V
+
–
when /V24 option is specifed.
NOTE
Do not use unassigned terminals as relay terminals.
7
8
Note: Connecting a 250
Ω
resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “22”).
Receiving 4-20 mA DC Current
Signals with the Controller
250
Ω
4-20mA
-
+
If the power is turned on, when the RUN/RESET external contact
input is ON, the controller is in runnig state. But Hold/Cancel
hold external contact input is ON, the controller is in cancelling
state.