
LED PR
LED R2
PRG
UP key
DOWN key
PR
R1
R2
AL
LED R1
LED AL
www.ako.com
1453H252 Ed.01
ON/OFF regulators, 4-20 mA input, 2 relays and acoustic alarm, for moisture, pressure, level, etc.
Devices designed to display, process control and regulation, with 4-20 mA input type for
sensors and converters. Both outputs with SPDT relays can be configured for two indepen-
dent stages, 2 related stages, neutral zone, or also as 1 stage + alarm.
Index
1 - Versions and references
6 - Menus, parameters and messages
2 - Technical data
7 - Parameter transfer
3 - Instalación
8 - Relay operation and control
4 - Front panel functions
9 - Maintenance
5 - Adjustment and configuration
10 - Warnings
1- VERSIONS AND REFERENCES
MODEL
RELAYS
POWER SUPPLY, 50/60 Hz
AKO-14532
8 A, 250 V, cos
ϕ
=1, SPDT
230 V~ ±10%
AKO-14534
8 A, 250 V, cos
ϕ
=1, SPDT
120 V~ +8% -12%
2- TECHNICAL DATA
Configuration range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . from -999 to 999
Resolution, Set Point and differential:. . . . . (0,1 from -99,9 to 99,9) (1 from -999 to 999)
Accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 %
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 VA
Working ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 50 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Control device classification: Independent mounting, with characteristic of automatic ope-
ration Type 1.B action, to be used in a clean situation, logical medium (software) class A
and continuous operation.
Double insulation between the power supply, secondary circuit and relay output.
Allocated pulse voltage: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800 V
Pressure ball test temperature:
Accessible parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts that position active elements: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 ºC
Voltage and current declared by the EMC tests:. . . . . . . . . . . . . . . . . . . . . 207 V, 16 mA
Current of radio jamming suppression test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270mA
3- INSTALLATION
The controller must be installed in a place protected from vibrations, water and corrosive
gases, and where ambient temperature does not surpass the value specified in the techni-
cal data.
In order for the controllers to have IP65 protection, the gasket must be properly installed
between the apparatus and the perimeter of the panel cut-out where it is to be fitted.
3.1 Fastening units for panel mounting:
GB
UP key
Press once to cancel the alarms, but they
remain displayed (optional by parameter
AtA
). When pressed for at least 5 seconds,
the
SP1
Set Point of Relay
R1
is displayed.
In programming, it increases the displayed
value.
DOWN key
Press once to cancel the alarms, but they
remain displayed (optional by parameter
5- ADJUSTMENT AND CONFIGURATION
It must only be programmed or modified by personnel who are fully conversant with the
equipment operation and possibilities.
5.1 Set Point configuration.
The factory SET POINT default value is 0.
- Press
key for at least 5 seconds to DISPLAY SET POINT in Relay R1 or
key for Relay
R2. It displays the CURRENT SET POINT value and LED “
PR
” starts flashing.
- Press
or
keys to CHANGE SET POINT to the required value.
LED R1: Relay 1 indicator enabled
LED AL: Alarm indicator enabled
LED R2: Relay 2 indicator enabled
LED PR: Flashing, programming phase
5.2 Parameter configuration
Level 1
Menus
- Press
+
keys simultaneously for at least 10 seconds. The LED “
PR
” will start flas-
hing, LEVEL 1 MENUS programming has been accessed and the first menu “
Po1
” is dis-
played.
- Press
key to access the next menu and
key to return to the previous one.
- Pressing
+
keys simultaneously in the last menu EP, the controller returns to the
VALUE DISPLAY status and LED “
PR
” will stop flashing.
When
PA
is displayed, the PASSWORD programmed in the
PAr
menu
PAS
parameter must
be entered to access LEVEL 1 MENUS programming.
- Press
+
keys simultaneously. 0 will be displayed to ENTER PASSWORD.
- Press
or
keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.
- Press
+
keys simultaneously to ACCEPT PASSWORD. The first menu “
Po1
” will be
displayed.
Level 2
Parameters
- In the desired menu of LEVEL 1 MENUS, press keys
+
simultaneously. LEVEL 2
PARAMETERS programming is accessed. The first parameter of the selected menu is dis-
played on the screen.
- Press
key to access the next parameter and
key to return to the previous one.
- Pressing
+
keys simultaneously in the last parameter EP, the controller returns to
LEVEL 1 MENUS.
Level 3
Values
- To DISPLAY CURRENT VALUE of any parameter, select the required one and press
+
keys simultaneously. Once it is displayed, you can CHANGE VALUE pressing
or
key.
- Press
+
keys simultaneously to ACCEPT THE NEW VALUE. The programming returns
to LEVEL 2 PARAMETERS.
To fix the unit, place the faste-
ners
1
over the sliders
2
as shown
in the figure. Move the fasteners
in the direction of the arrow. By
pressing tab
3
fasteners may be
moved in the opposite direction of
the arrow.
3.2 Connection:
See diagram on the unit rating plate.
The probe or 4-20 mA output converter and its leads should
NEVER
be installed in ducting
together with power, control or power supply wiring.
The power supply circuit must be connected with a minimum 2 A, 230 V switch located
close to the unit. Power supply cables must be H05VV-F 2x0,75 mm
2
or H05V-K 1x0,75 mm
2
.
Section of connecting wires for relays contacts must range from 1 mm
2
to 2.5 mm
2
.
NOTE: If no key is pressed for 25 seconds in either of the previous steps, the controller will
automatically return to the VALUE DISPLAY status without modifying any of the parameter
values.
PANEL CUT-OUT
3
2
1
max. 18 mm
61,5
44
28,5
70,5
4- FRONT PANEL FUNCTIONS
AtA
). When pressed for at least 5 seconds, the
SP2
Set Point of Relay
R2
is displayed. In
programming, it decreases the displayed value.
5 Sec.
VALUE
DISPLAY
DISPLA
Y SP1
Relay
R1
SET POINT
CHANGE SET POINT
ACCEPT THE NEW
CURRENT
SET POINT
NEW
SET POINT
SIMULTANEOUSLY
5 Sec.
DISPLA
Y SP2
Relay
R2
SET POINT
- Press + keys
simultaneously to
ACCEPT THE NEW
SET POINT. The dis-
play returns to the
the VALUE DISPLAY
status and LED
“
PR
” stops flas-
hing.
10 Sec.
CHANGE NUMBER
DISPLA
Y
PARAMETER
PASSWORD
REQUEST
ENTER
PASSWORD
DISPLAY
PASSWORD
CURRENT
VALUE
NEW
VALUE
IF PAS=0
SIMULTANEOUSLY
ACCEPT THE NEW
VALUE
DISPLAY
LEVEL 1
MENUS
LEVEL 3
VALUES
EXIT
PROGRAMMING
ACCEPT
PASSWORD
PASSWORD
IF PROGRAMMED
CHANGE V
ALUE
SIMULTANEOUSLY
SIMULTANEOUSLY
SIMULTANEOUSLY
SIMULTANEOUSLY
LEVEL 2
PARAMETERS
SIMULTANEOUSLY
DISPLA
Y
VALUE
EXIT TO
LEVEL 1