Precautions to Be Taken While Wiring

Take the following precautions when wiring the input signal 

cables.

●  With a screw terminal, we recommend that you use a 

crimp-on lug with an insulation sleeve (M4 for power 

supply wiring, M3 for signal wiring).

 

Crimp-on lug with an insulation sleeve

Recommended signal 

wiring crimp-on lug

N1.25-MS3 (JST Mfg. Co., Ltd.)

●  With a clamp terminal, we recommend the following wire.

GX90XA

Cross-sectional area

0.05 mm

2

 to 1.5 mm

2

 (AWG30 to 16)

Stripped wire length

5 to 6 mm

GX90XD, GX90XP, GX90YA

Cross-sectional area

0.2 mm

2

 to 1.5 mm

2

 (AWG24 to 16)

Stripped wire length

9 to 10 mm

RS-422/485 (/C3 option)

Cross-sectional area

0.08 mm

2

 to 1.5 mm

2

 (AWG28 to 16)

Stripped wire length

6 to 7 mm

●  When wiring input/output signal cables, observe the 

minimum bend radius of the cables. For the minimum 

bend radius, use the specifications indicated by the cable 

manufacture or six times the cable conductor diameter, 

whichever is larger.

●  Take measures to prevent noise from entering the 

measurement circuit.

•  Move the measurement circuit away from the power 

cable (power circuit) and ground circuit.

•  Ideally, the object being measured should not generate 

noise. However, if this is unavoidable, isolate the 

measurement circuit from the object. Also, ground the 

object being measured.

•  Shielded wires should be used to minimize the noise 

caused by electrostatic induction. Connect the shield to 

the ground terminal of the GM as necessary (make sure 

you are not grounding at two points).

•  To minimize noise caused by electromagnetic induction, 

twist the measurement circuit wires at short, equal 

intervals.

•  Make sure to earth ground the protective ground 

terminal through minimum resistance.

●  When using internal reference junction compensation on 

the thermocouple input, take measures to stabilize the 

temperature at the input terminal.

•  Always use the terminal cover.

•  Do not use thick wires which may cause large heat 

dissipation (we recommend a cross sectional area of 

0.5 mm

2

 or less).

•  Make sure that the ambient temperature remains 

reasonably stable. Large temperature fluctuations can 

occur if a nearby fan turns on or off.

●  Connecting the input wires in parallel with other devices 

can cause signal degradation, affecting all connected 

devices. If you need to make a parallel connection, then

•  Turn the burnout detection function off.

•  Ground the instruments to the same point.

•  Do not turn other instruments on or off during operation. 

This can have adverse effects on the other instruments.

•  RTD or resistance input cannot be wired in parallel.

Removing and Attaching a Terminal Cover

Removing the Terminal Cover

  Loosen the screw at the bottom section of the terminal 

cover, and remove the cover.

Attaching the Terminal Cover

A

The shape of the cover varies depending on 

the module, but the procedure is the same.

1. Insert the two hooks at the top section 

on the inside of the terminal cover into 

A, and push the bottom section of the 

terminal cover.

2. Fasten the screw at the bottom section 

of the terminal cover to fix the cover in 

place.

Recommended tightening torque: 

 0.6 N•m

Removing and Attaching a Terminal Block

Removing the GX90XA/GX90WD/GX90UT Terminal 

Block

  Push down on the lever at the bottom section of the 

module, and pull the terminal block out.

Attaching the GX90XA/GX90WD/GX90UT Terminal 

Block

  Insert the terminal block into the module, and push the 

lever firmly against the module (at the position indicated by 

the arrow in the figure).

 

Terminal block release lever

Side view of module

For modules other than the GX90XA, you can use the 

attachment screw to remove and attach them.

 

Terminal block attachment screw

  Recommended torque for tightening the terminal block 

attachment screws: 0.1 N•m

Содержание SMARTDAC+ GM10

Страница 1: ...ail 14 Mounting on a Wall 14 Wiring 15 Precautions to Be Taken While Wiring 16 Removing andAttaching a Terminal Cover 16 Removing andAttaching a Terminal Block 16 Wiring Procedure 17 Internal dimensio...

Страница 2: ...out prior notice as a result of continuing improvements to the instrument s performance and functions Every effort has been made in the preparation of this manual to ensure the accuracy of its content...

Страница 3: ...ration or shock or pull out the card Data can become corrupt or permanently lost Only use Yokogawa SD cards Operation cannot be guaranteed with other brands of card When inserting the SD card into the...

Страница 4: ...iption GM90PS Power Supply Module for SMARTDAC GM Type 1 Always 1 Area N General Supply voltage 1 100 240V AC 2 12 28 V DC 1 Power supply connection D Power inlet with UL CSA cable F Power inlet with...

Страница 5: ...01 1 1GB Shunt resistor for M3 screw terminal 415940 1 250 0 1 415941 1 100 0 1 415942 1 10 0 1 Shunt resistor for clamp terminal 438920 1 250 0 1 438921 1 100 0 1 438922 1 10 0 1 GM10 Style Number Re...

Страница 6: ...system A unit consisting of a GM10 a GM90PS and a GX90EX Up to six I O modules can be connected to a unit Up to six sub units can be connected via the GX90EX Sub Unit multi unit system A unit consist...

Страница 7: ...not be detected GM10 1 If you want to use the DI of a GX90XD or GX90WD only a single module installed in the GM main unit can be used Do not link modules in a way that violates the specifications Doi...

Страница 8: ...or both do so before setting the date and time Download the following software applications SMARTDAC Standard Hardware Configurator SMARTDAC Standard IP Address Configurator See the list of electroni...

Страница 9: ...e IM 04L55B01 01EN The multi unit system support only cascaded connections If connected in a ring none of the sub units will be identified Link the GX90EX to the left end on a main unit and next to th...

Страница 10: ...e Expand reduce button 2 Click a No The corresponding GM10 is enabled 3 Click Network Config and set the items on the address setting screen For details on the settings see the IP Address Configurator...

Страница 11: ...er 1 and click the button under Channel set Channel number display The Group number 1 Channel set dialog box appears 3 Set AI channel 001 to 0010 to On and click OK The selected channels appear under...

Страница 12: ...unication Reconfiguration dialog box appears click OK The setup data of the connected GM will appear 3 Set the items 4 On the menu bar click the Setting tab and then Send Settings 5 When a Communicati...

Страница 13: ...hese kinds of circumstances wait for at least an hour before using the GM to acclimate it to the surrounding environment Well Ventilated Location To prevent overheating install the GM in a well ventil...

Страница 14: ...ront DIN rail DIN rail Rear of GM Click Check that all the latches are securely fastened to the DIN rail Removing from the DIN Rail 1 Lower the latch on the rear panel of the GM using a flat blade scr...

Страница 15: ...ed For all other signal cables use basic insulated cables dielectric strength of 1390 VAC To prevent electric shock attach the terminal cover after wiring and make sure not to touch the ter minals App...

Страница 16: ...n the thermocouple input take measures to stabilize the temperature at the input terminal Always use the terminal cover Do not use thick wires which may cause large heat dissipation we recommend a cro...

Страница 17: ...ection port and tighten the screw terminal Wiring to a GX90XA Analog Input Module Universal Low withstand voltage relay Electromagnetic relay Current mA type Terminal Diagram CH1 301 201 101 101 102 1...

Страница 18: ...A B B b A 5 DC current input with an external shunt resistor Be careful because the DI wiring is different between level and contact Terminal Arrangement M3 screw terminal CH No Term No Symbol Term N...

Страница 19: ...DI8 COM COM DI9 DI16 COM DI9 DI16 DI1 DI8 COM Wiring direction Wiring direction 11 19 11 19 21 29 21 29 Terminal Arrangement Term No Symbol Term No Symbol 21 DI9 11 DI1 22 DI10 12 DI2 23 DI11 13 DI3...

Страница 20: ...CH2 CH3 CH4 CH5 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH6 CH7 CH8 CH9 CH10 11 20 11 20 21 30 21 30 M3 screw terminal Clamp terminal Wiring direction Wiring direction Terminal Arrangement Term No S...

Страница 21: ...on Internal circuit Connecting to the RS 422 485 Connector C3 option Two wire system Four wire system Electric potential of the shield Shield FG SDB SG SDA RDB RDA Electric potential of the shield Shi...

Страница 22: ...rovide a power switch double pole type on the power supply line to separate the GM from the main power supply Use labels to indicate that this switch is for cutting off the power supply to the GM and...

Страница 23: ...Power On and Off If the power switch of GM GX60 systems under operation be turned on or off carelessly it may result the system down or injury Check the following points before turning on the power s...

Страница 24: ...L Red Lights during an error Setting Switches Dipswitches Use the dipswitches to set the unit number of the expansion module 10 Mbps fixed mode and operation mode master slave Dipswitch Settings Dipsw...

Отзывы: