7-28
IM CW120-E
7.2.16 Setting Decimal Point Position and Unit of Electric Energy (
)
Description
You can set the decimal point position and unit of the electric energy
readings.
Select
(default) when using the standard settings. Selecting the
standard setting lets the CW120/121 power meter determine the decimal
point position and unit based on the product of [rated power
×
VT ratio
×
CT
ratio
×
1.3] as follows.
Rated Power
×
VT Ratio
×
CT Ratio
×
1.3 Decimal Point Position and Unit
1 to 9.999
10 to 99.99
100 to 999.9
1 to 9.999
10 to 99.99
100 to 999.9
1 to 9.999
10 to 99.99
100 to 999.9
1 to 9.999
10 to 99.99
100 to 9999
W
W
W
kW
kW
kW
MW
MW
MW
GW
GW
GW
to 9999.99
to 99999.9
to 999.999
to 9999.99
to 999.999
to 9999.99
to 99999.9
to 999.999
to 9999.99
to 9999.99
to 99999.9
to 999999
0.00
0.0
0.000
0.00
0.000
0.00
0.0
0.000
0.00
0.00
0.0
0
Wh
Wh
kWh
kWh
kWh
MWh
MWh
MWh
GWh
GWh
GWh
GWh
When specifying the desired decimal point position and unit, select:
• Decimal position setting from 000.000, 0000.00, 00000.0, and 000000.
• Unit from Wh, kWh, MWh, and GWh.
Procedure
(1) Using the
keys, make the
mark and its current settings
appear on the screen. Then, press the
key.
or the number
representing the currently set decimal point position flashes.
7.2 Setting Each Item