<3.Construction and Function>
3-9
IM 11R02A01-02E
5th Edition : Dec. 28, 2016-00
3.4.2
High/Low Alarm Action
Higher and lower alarm limits are set for the amplified thermocouple output, respectively, to
execute a sequence.
The higher alarm limit is the point to alarm the excessive combustion of the burner, which is set to
approximately 120% of the span. The lower alarm limit is the point to alarm the flame extinction
of the burner. You can change the limit by “LOW AL”volume on the front panel of the calorie
detector. However, the lower alarm limit is set to an appropriate value in the final adjustment test
at the factory before shipment.
If the higher or lower limit alarm occurs, the electromagnetic valve (EV) is closed to stop the
supply of gas
3.4.3 Ignition
Press START on the front panel of the calorie detector to start ignition. One cycle of an
ignition constitutes (T1) and (T2). (T1) is when the ignition voltage is applied to the heater
(T1). (T2) is when the voltage is not applied (when using low calorific value, the time when the
preheating voltage is applied). The cycle repeats five times normally. (T1) time and (T2) time
are set independently within the range from approximately 2 to 20 seconds depending on the
measurement range and gas composition.
If the amplified thermocouple output exceeds the lower alarm limit, the burner is determined to
be ignited and the ignition action is stopped even if it is not completed. If the burner is not ignited
even after the ignition voltage is applied five times, the ignition action is stopped after the ignition
voltage is applied for the fifth time. In that case, press START to start the ignition again.
If the burner flame is extinguished in the event of an alarm, after removing the cause of the
failure, press START to start the ignition again. If the alarm occurs due to excessive combustion,
you cannot resume the ignition until the thermocouple output falls below the lower alarm limit (*1).
Indication lamps turn ON or OFF in accordance with each stage of the sequence.
Figure 3.11 shows the ignition sequence for which the lower alarm limit is set to 50%.
Ignition voltage
EV
ALARM lamp
MEAS lamp
Ignition action
Alarm
status
Measurement
status
ON
OFF
ON
OFF
ON
OFF
Open
Hi
Low
T1T2
Time
Thermocouple output
120%
Close
Ignition action starts
Ignition action starts
Not ignition
Ignitied
Excessive
combustion
*1
Alarm status
(Higher alarm limit)
50%
(Lower alarm limit)
IGNIT lamp
Ignition action
Figure 3.11 Ignition Sequence