12 Drive Control, Duty Modes, and Programming
YASKAWA ELECTRIC
TOEP C710617 17B YASKAWA AC Drive GA700 Initial Steps
EN 27
No.
(Hex.)
Name
Description
b1-04
(0183)
Reverse Operation
Selection
Enables and disables reverse operation. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0: Reverse Enabled, 1: Reverse Disabled
C1-01
(0200)
RUN
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the time to start S-curve acceleration.
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the time to complete S-curve acceleration.
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the time to start S-curve deceleration.
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the time to complete S-curve deceleration.
C6-01
(0223)
Normal / Heavy Duty
Selection
Sets the drive duty rating.
0: Constant Torque Application Heavy Duty Rating 1 (HD1 / HD2),
1: Variable Torque Application Normal Duty Rating 1 (ND1 / ND2)
C6-02
(0224)
Carrier Frequency
Selection
Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz), 3: 8.0 kHz (6.0 kHz), 4: 10.0 kHz (8.0 kHz),
5: 12.5 kHz (10.0 kHz), 6: 15.0 kHz (12.0 kHz), 7: Swing PWM1 (Audible Sound 1),
8: Swing PWM2 (Audible Sound 2), 9: Swing PWM3 (Audible Sound 3),
A: Swing PWM4 (Audible Sound 4), F: User Defined (C6-03 to C6-05)
d1-01 - d1-16
(0280 - 0291)
RUN
Reference 1 to 16
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency Display Unit
Selection]
. Set
H1-xx = 6 [Terminal Sx Function Selection = Jog Reference Selection]
to
use the Jog frequency reference.
d2-01
(0289)
Frequency Reference
Upper Limit
Sets maximum limit for all frequency references. This value is a percentage of
E1-04
[Maximum Output Frequency]
.
d2-02
(028A)
Frequency Reference
Lower Limit
Sets minimum limit for all frequency references. This value is a percentage of
E1-04
[Maximum Output Frequency]
.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage. Set this parameter to the nominal voltage of the AC power
supply.
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
E1-05
(0304)
Maximum Output Voltage Sets the maximum voltage for the V/f pattern.
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
E2-01
(030E)
Motor Rated Current
Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power (kW)
Sets the motor rated power in 0.01 kW units. (1 HP = 0.746 kW)
H1-01 - H1-08
(0438, 0439,
0400 - 0405)
Terminal Sx Function
Selection
Sets the functions for MFDI terminals S1-S8.
EN