10 Electrical Installation

EN 18

YASKAWA ELECTRIC

TOEP C710617 17B YASKAWA AC Drive GA700 Initial Steps

10

Electrical Installation

DANGER

Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before

servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make
sure that the drive is safe. Failure to obey will cause death or serious injury.

DANGER

Electrical Shock Hazard. Make sure that all electrical connections are correct and install all drive covers

before energizing the drive. Use terminals for their intended function only. Incorrect wiring or ground connections, and incorrect
repair of protective covers can cause death or serious injury.

WARNING

Electrical Shock Hazard. Correctly ground the drive before turning on the EMC filter switch. Failure to obey

can cause death or serious injury.

WARNING

Electrical Shock Hazard. Use the drive terminals only for their intended function. Refer to the drive Technical

Manual for more information about I/O terminals. Incorrect wiring, incorrect grounding, and unsatisfactory repair of the
protective cover could cause death or serious injury and damage to the drive.

Standard Connection Diagram

Wire the drive as shown in the following figure. If the drive is run using the keypad, the motor can be run by main
circuit wiring.

WARNING

Sudden Movement Hazard. Set the multi-function input terminal parameters before closing the control circuit

wiring. Incorrect Run/Stop circuit sequence settings can cause death or serious injury from moving equipment.

WARNING

Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before energizing the drive.

Momentarily closing a digital input terminal can start a drive that is programmed for 3-Wire control. Failure to obey can cause
death or serious injury from moving equipment.

WARNING

Sudden Movement Hazard.

When using a 3-Wire sequence:

• Set the drive for 3-Wire sequence.
• Set b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command]
• Wire the drive for 3-Wire sequence.

The motor can rotate in reverse when energizing the drive if these three conditions are true:

• The drive is wired for 3-Wire sequence.
• The drive is set for a 2-Wire sequence (default).
• b1-17 = 1 [Accept Existing RUN Command]

Failure to obey can cause death or serious injury from moving equipment.

WARNING

Sudden Movement Hazard. Make sure that the drive I/O signals and external sequence are correct before

entering the Application Preset function. Entering the Application Preset function or setting A1-06

0 [Application Preset

General-purpose] changes the drive I/O terminal functions and can cause sudden equipment operation. Failure to obey can
cause death or serious injury.

NOTICE

Fire Hazard. Install sufficient branch circuit short circuit protection as specified by applicable codes and this

manual. The drive is suited for circuits that supply not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V
Class), 480 Vac maximum (400 V Class). Failure to obey can cause death or serious injury.

NOTICE

When the input voltage is 440 V or higher or if the wiring distance is longer than 100 m (328 ft.) be sure to use

a drive duty motor or carefully monitor the motor insulation voltage. Failure to obey can cause damage to the motor insulation.

NOTICE

Do not connect the AC control circuit ground to the drive enclosure. Failure to obey can cause incorrect

control circuit operation.

Содержание GA700 GA700 Series

Страница 1: ...Performance Type Initial Steps Type CIPR GA70Cxxxxxxxx Models 200 V class 0 55 to 110 kW 400 V class 0 55 to 355 kW To properly use the product read this manual thoroughly and retain for easy referen...

Страница 2: ...ll products that are designed to incorporate parts manufactured by Yaskawa must be provided to the end user and include proper warnings and instructions regarding their safe use and operation All warn...

Страница 3: ...cuit Failure to obey can cause death or serious injury WARNING Electrical Shock Hazard Use a type B Residual Current Monitor Residual Current Device RCM RCD for protection against contact when using a...

Страница 4: ...round connections and incorrect repair of protective covers can cause death or serious injury WARNING Electrical Shock Hazard Do not make changes to the drive body or drive circuitry Failure to obey c...

Страница 5: ...number in the MODEL section of the drive nameplate to make sure that you received the correct model Contact your supplier if you receive the incorrect drive model or if the drive does not operate cor...

Страница 6: ...and from the MFDI terminals when the drive is not in Drive Mode Received a Fast Stop command Output is shut off from the safety function Is operating in REMOTE Mode and the user pushed on the keypad I...

Страница 7: ...drive operation Note Uses a stop priority circuit will stop the drive quickly in LOCAL or REMOTE Mode The drive will not stop with when o2 02 0 STOP Key Function Selection Disabled H Left Key Moves th...

Страница 8: ...6 Keypad EN 8 YASKAWA ELECTRIC TOEP C710617 17B YASKAWA AC Drive GA700 Initial Steps Keypad Mode and Menu Displays Figure 6 2 Keypad Functions and Display Levels...

Страница 9: ...while in Programming Mode Set b1 08 0 Disregard RUN while Programming to reject the Run command from an external source while in Programming Mode default Set b1 08 1 Accept RUN while Programming to ac...

Страница 10: ...C RUN Illuminated The drive is in regular operation Flashing 1 When the drive is decelerating to stop The drive received a Run command but the frequency reference is 0 Hz When the drive received a DC...

Страница 11: ...ically set these functions Control Method Selection Normal Heavy Duty Selection Motor Parameters Speed reference source Run command source Acceleration and Deceleration Times 5 Run the motor without a...

Страница 12: ...rect operation and damage to electrical devices Installation Position and Distance Install the drive vertically for sufficient cooling airflow Note Contact Yaskawa or a Yaskawa representative for more...

Страница 13: ...environment is crucial to ensure proper performance and the expected lifespan of the product Ensure the installation environment satisfies the following specifications Environment Conditions Area of U...

Страница 14: ...rom electrical interference if components must be near the drive Failure to obey can cause incorrect operation NOTICE Do not let unwanted objects for example metal shavings or wire clippings fall into...

Страница 15: ...Keypad connector B Hook C Connector holder Figure 9 5 Remove the Front Cover 6 Remove the wiring cover before wiring the main circuit terminal A Wiring cover Remove the Terminal Cover 1 Loosen the scr...

Страница 16: ...before operating the drive Reattach the Front Cover 1 Reattach the wiring cover 2 Reattach the front cover to the drive with the supplied screws 3 Remove the keypad connector from the connector holder...

Страница 17: ...not maintain the IP20 protective level Hold the cutaway section of the wiring cover firmly to prevent scattering when clipping this section There is a risk of injury from scattering of the cutaway sec...

Страница 18: ...Stop circuit sequence settings can cause death or serious injury from moving equipment WARNING Sudden Movement Hazard Correctly wire the start stop and safety circuits before energizing the drive Mom...

Страница 19: ...end that the sequence that shuts off the power source be set via the fault relay output for the drive When using the Auto Restart function if L5 02 1 Auto Restart Fault output active the fault signal...

Страница 20: ...Sourcing mode Short terminals SC and SN External power supply No jumper necessary 12 The maximum output current capacity of the Vand V terminals on the control circuit terminal is 20 mA NOTICE Do not...

Страница 21: ...ndard specifies that users must wire the power supply to automatically turn off when the protective ground wire disconnects Users can also connect a protective ground wire that has a minimum cross sec...

Страница 22: ...to equipment A Terminal block TB2 3 B Terminal block TB2 2 C Terminal block TB2 1 D DC bus voltage terminals configuration changes by drive model E Drive ground terminals F Motor case ground G Three p...

Страница 23: ...tery or an equivalent battery with the following characteristics Nominal voltage 3 V Work temperature range 20 C to 85 C 4 F to 185 F Nominal battery life 2 years 20 C 68 F ambient temperature 3 Selec...

Страница 24: ...lable YES Stationary Line Line Resistance 2 Select this tuning mode when The drive and motor capacities are different The drive is in V f Control Replacing the drive and motor YES YES Table 11 2 EZ Tu...

Страница 25: ...and maximum value 8 Push to keep the changes 9 Continue to set parameters or push Back to go back to the HOME screen 12 Drive Control Duty Modes and Programming Drive Control Methods This section give...

Страница 26: ...utput current for 60 s Normal Duty 2 Rating ND2 460 Vand 480 V Drive Parameters Refer to the table when setting the most important parameters Note Users can change parameters with RUN in the No column...

Страница 27: ...ible Sound 1 8 Swing PWM2 Audible Sound 2 9 Swing PWM3 Audible Sound 3 A Swing PWM4 Audible Sound 4 F User Defined C6 03 to C6 05 d1 01 d1 16 0280 0291 RUN Reference 1 to 16 Sets the frequency referen...

Страница 28: ...Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3 H3 08 0416 RUN Terminal A3 Bias Setting Sets the bias of the analog signal input to MFAI terminal A3 H3 09 0417 T...

Страница 29: ...n oL1 time Usually it is not necessary to change this setting L3 04 0492 Stall Prevention during Decel Sets the method that the drive will use to prevent overvoltage faults when decelerating 0 Disable...

Страница 30: ...rom the host controller is correct and the controller set the two signals correctly If the signals are correct and the alarm continues to occur replace the drive oC Overcurrent There is a short circui...

Страница 31: ...or a Yaskawa representative to replace the main capacitors Make sure that there are no problems with the drive input power If drive input power is correct and the alarm continues to occur replace the...

Страница 32: ...are subject to change without notice for ongoing product modifications and improvements 2016 YASKAWA Electric Corporation MANUAL NO TOEP C710617 17B 1 0 Published in Japan September 2016 15 11 8_YEU O...

Отзывы: