A - 50 mm (2 in.) minimum
B - 30 mm (1.2 in.) minimum on both
sides
C - 2 mm (0.08 in.) minimum between
each drive
D - 120 mm (4.7 in.) minimum above
and below
Figure 9.3 Installation Distances for Multiple Drives (Side-by-Side)
Note:
•
Align the tops of drives that have different dimensions to help when replacing cooling fans.
•
Remove the top protective covers of all drives when mounting UL Type 1 enclosure drives side-by-side.
Figure 9.4 Enclosed Wall-Mounted Type (UL Type 1) Installed Side-by-Side
◆
Installation Environment
The installation environment is crucial to ensure proper performance and the expected lifespan of the product.
Ensure the installation environment satisfies the following specifications.
Environment
Conditions
Area of Use
Indoors
Power supply
Overvoltage Category III
Ambient Temperature
Setting
Open chassis type (IP20): -10°C to +50 °C (14 °F to 122 °F)
Enclosed wall-mounted type (UL Type 1): -10 °C to +40 °C (14 °F to 104 °F)
•
Drive reliability improves in environments without wide temperature fluctuations.
•
When using the drive in an control panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
•
Do not allow ice to develop on the drive.
•
Derate the output current and output voltage to install the drive in areas with ambient temperatures up to 60 °C
(140 °F).