12 Drive Control, Duty Modes, and Programming
EN 28
YASKAWA ELECTRIC
TOEP C710617 17B YASKAWA AC Drive GA700 Initial Steps
No.
(Hex.)
Name
Description
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0: 0 to 10 V (Lower Limit at 0), 1: -10 to +10 V (Bipolar Reference), 2: 4 to 20 mA,
3: 0 to 20 mA
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
H3-03
(0411)
RUN
Terminal A1 Gain Setting Sets the gain for the analog signal input to MFAI terminal A1.
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
H3-05
(0413)
Terminal A3 Signal Level
Select
Sets the input signal level for MFAI terminal A3.
0: 0 to 10 V (Lower Limit at 0), 1: -10 to +10 V (Bipolar Reference), 2: 4 to 20 mA,
3: 0 to 20 mA
H3-06
(0414)
Terminal A3 Function
Selection
Sets the function for MFAI terminal A3.
H3-07
(0415)
RUN
Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3.
H3-08
(0416)
RUN
Terminal A3 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A3.
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
0: 0 to 10 V (Lower Limit at 0), 1: -10 to +10 V (Bipolar Reference), 2: 4 to 20 mA,
3: 0 to 20 mA
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2.
H3-11
(0419)
RUN
Terminal A2 Gain Setting Sets the gain of the analog signal input to MFAI terminal A2.
H3-12
(041A)
RUN
Terminal A2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A2.
H3-13
(041B)
Analog Input FilterTime
Constant
Sets the time constant for primary delay filters on MFAI terminals.
H3-14
(041C)
Analog Input Terminal
Enable Sel
Sets which Sx terminal is enabled when
H1-xx = C [Terminal Sx Function Selection =
Analog Terminal Enable Selection]
. Also sets which Sx terminal is disabled when the input
is OFF.
1: Terminal A1 only, 2: Terminal A2 only, 3: Terminals A1 and A2, 4: Terminal A3 only,
5: Terminals A1 and A3, 6: Terminals A2 and A3, 7: Terminals A1, A2, and A3
H4-01
(041D)
Terminal FM Analog
Output Select
Sets which drive monitor
Ux-xx
to output from MFAO terminal FM.
H4-02
(041E)
RUN
Terminal FM Analog
Output Gain
Sets the gain of the
Ux-xx
monitor signal in
H4-01
.