3.9 Control I/O Connections
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
79
El
ec
tr
ical
I
n
st
al
lat
ion
3
3.9 Control I/O Connections
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in
(Default: Sink mode, internal power supply).
Note:
Never short terminals SP and SN as doing so will damage the converter.
Table 3.13 Digital Input Sink / Source / External Power Supply Selection
◆
Terminal A2 Input Signal Selection
Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained
in
. Set parameter H3-09 accordingly as shown in
. Refer to
To set the DIP switch, use tweezers or a tool with a tip width of approximately 0.8 mm.
Figure 3.41
Figure 3.38 DIP Switch S1
Table 3.14 DIP Switch S1 Settings
Converter Internal Power Supply (Terminal SN
and SP)
External 24 Vdc Power Supply
Sinking Mode (NPN)
Sourcing Mode (PNP)
Setting
Description
V (left position)
Voltage input (-10 to +10 V or 0 to 10 V)
I (right position)
Current input (4 to 20 mA or 0 to 20 mA): default setting
SC
S8
S7
24 Vdc
SP
SN
YAI
SC
S8
S7
24 Vdc
SP
SN
External
24 Vdc
YAI
SC
S8
S7
24 Vdc
SP
SN
YAI
SC
S8
S7
24 Vdc
SP
SN
External
24 Vdc
YAI
DIP switch S1
V
I