B.2 Parameter Tables
178
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
◆
d: References
Reference parameters set the value of the DC bus voltage reference.
◆
F: Options
F parameters program the converter for communication options and to function with option cards.
C7-43
(112AH)
Input Voltage Offset
Adjustment
Vac Bias Adj Sel
There is normally no need to change this parameter from
the default value. This parameter is for factory setting.
If the setting is not correct, the converter may be damaged.
0: Standard
1: Start offset adjustment. (The parameter returns to 0 after
it is set.)
2: Offset adjustment not required. (The parameter returns
to 0 after it is set.)
Default: 0
Range: 0 to 2
C7-44
(112BH)
Gain for Active
Damping 3
Damping Gain 3
There is normally no need to change this parameter from
the default value.
Default: 0.00
Min.: 0.00
Max.: 1.00
C7-47
(112EH)
Adjustment Reactor
1
L1 Compensation
There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.
Min.: 00.000
Max.: 65.000
C7-50
(113BH)
Converter Ready
ON Delay Time
Conv READY delay
Sets the delay time to turn on the Converter Ready signal
(H2-
=6).
Default: 0 ms
Min.: 0
Max.: 500
C7-51
(113CH)
Adjustment Reactor
2
L2 Compensation
There is normally no need to change this parameter from
the default value.
Set this parameter to the value that is specified by the
manufacturer when using a filter such as the DC5.
Min.: 00.000
Max.: 65.000
<1> This parameter is not available in model 4A0630.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
d8: DC Bus Voltage Reference
d8-01
(2B9H)
DC Bus Voltage
Reference
Vpn Volt Ref
Sets the DC bus voltage reference in volts.
Yaskawa recommends setting a value that is 1.5 times the
set value of the Power Supply Voltage (U1-54).
200 V Class
Default: 330 V
Range:300 V to
360 V
400 V Class
Default: 660 V
Range: 600 V to
730 V
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
F4: Analog Monitor Card (AO-A3)
F4-01
(391H)
Terminal V1
Monitor Selection
AO Ch1 Select
Sets the monitor signal for output from terminal V1. Set
this parameter to the last three digits of the desired
U
-
monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
No.
(Addr.
Hex)
Name
LCD Display
Description
Values