TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
3.6 Main Circuit Wiring
3.6 Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit
in the converter.
NOTICE:
Do not solder the ends of wire connections to the converter. Soldered wiring connections can loosen over time. Improper
wiring practices could result in converter malfunction due to loose terminal connections.
◆
Main Circuit Terminal Functions
Table 3.2 Main Circuit Terminal Functions
◆
Protecting Main Circuit Terminals
■
Insulation Caps or Sleeves
Use insulation caps or sleeves when wiring the converter with crimp terminals. Take particular care to ensure that the
wiring does not touch nearby terminals or the surrounding case.
■
Insulation Barrier
Insulation barriers are packaged with models 4A0270 to 4A0630 to provide added protection between terminals.
Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to
and
for instructions on placement of the insulation barriers.
Terminal
Type
Function
Page
200 V
Class
Model
2A0005 to 2A0130
400 V
Class
4A0005 to 4A0630
R/L1
Main circuit power supply input
These are the power supply input terminals that connect to
the input reactor.
S/L2
T/L3
r1/ 11
Power supply voltage detection inputs
These terminals are to detect the power supply voltage order
and voltage levels.
1/ 21
t1/ 31
–
DC voltage output
These terminals output a DC voltage
–
+
For 200 V class: 100
Ω
or less
For 400 V class: 10
Ω
or less
Grounding terminal