B.2 Parameter Tables
186
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
L8-10
(4B6H)
Heatsink Cooling
Fan Operation
Selection
Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On
0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the
converter is powered up.
Default: 0
Min.: 0
Max.: 1
L8-11
(4B7H)
Heatsink Cooling
Fan Off Delay Time
Fan Delay Time
Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.
Default: 60 s
Min.: 0 s
Max.: 300 s
L8-12
(4B8H)
Ambient
Temperature Setting
Ambient Temp
Enter the ambient temperature. This value adjusts the oL2
detection level.
Default: 40
°
C
Min.: -10
°
C
Max.: 50
°
C
L8-35
(4ECH)
Installation Method
Selection
Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
3: ExternalHeatsink
0: IP00/IP20/Open-Chassis Enclosure
1: Side-by-Side mounting
3: External Heatsink Installation
Min.: 0
Max.: 3
L8-41
(4F2H)
High Current Alarm
Selection
High Cur Alm Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled. An alarm is triggered at output currents above
150% of converter rated current.
Default: 0
Min.: 0
Max.: 1
L8-65
(66FH)
Power Supply Fault
Detection Selection
Vpn Ripple Sel
0: Disabled
1: Coast to Stop
2: Alarm Only
There is normally no need to change this parameter from
the default value.
Monitors the ripple of DC BUS voltage and detects Input
Power Supply Fault(PF2) when the ripple is too bad.
0: No detection
1: Stop operation (fault)
2: Continue operation (minor fault)
Default: 0
Min.: 0
Max.: 2
L8-66
(670H)
Power Supply Fault
Detection Voltage
Level
Vpn Ripple Lvl
There is normally no need to change this parameter from
the default value. The main circuit DC voltage ripple is
monitored in a cycle of 200 ms. If the difference between
the maximum and minimum values of the ripple exceeds
the value that is set in L8-66 for the number of times that is
set in L8-67, a power supply fault is detected.
200V Class
Default: <1>
Min.: 1
Max.: 200
400V Class
Default: <1>
Min.: 1
Max.: 200
L8-67
(671H)
Number of Times of
Power Supply Fault
for Detection
Vpn Ripple Cnt
Default: 5
Min.: 1
Max.: 10
L8-69
(673H)
Input Phase Loss
Protection Selection
3
AC Phase Imb Det
0: Disabled
1: Enabled
Sets whether to enable or disable the protective function
for the converter when there is an input phase loss.
0: Disabled
1: Enabled (Detect input phase loss and power supply
imbalance.)
Default: 1
Min.: 0
Max.: 1
L8-78
(2CCH)
Module Phase Loss
(LF3) Protection
LF3 Det Sel
0: Disabled
1: Enabled
Enables phase loss protection for the input terminals R/L1,
S/L2, T/L3 or R1/L11, S1/L21, T1/L31.
0: Disable
1: Enable
Note:
This parameter is available in model 4A0630.
Default: 1
Min.: 0
Max.: 1
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values