A.2 Converter Specifications
170
YASKAWA ELECTRIC
TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Environment
Area of Use
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10
°
C to +50
°
C (14
°
F to 122
°
F)
IP20/Open Type enclosure: -10
°
C to +40
°
C (14
°
F to 104
°
F)
Humidity
95 RH% or less (no condensation)
Vibration/Shock
10 to 20 Hz at 9.8 m/s
2
, 20 to 55 Hz at 5.9 m/s
2
(2A0005 to 2A0050, 4A0005 to 4A0100)
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 2.0 m/s
2
(2A0065 to 2A0130, 4A0130 to 4A0370)
10 to 20 Hz at 5.9 m/s
2
, 20 to 55 Hz at 2.0 m/s
2
(4A0630)
Storage Temperature
-20
°
C to +60
°
C (-4
°
F to +140
°
F)
Altitude
1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating.
Protection Design
IP00/Open Type enclosure
IP20/Open Type enclosure
Safety Standard
UL508C, IEC/EN61800-5-1, IEC/EN61800-3, CSA
<1> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the converter is powered up while a
ground fault is present at the output.
Item
Specification