8.2
Programming Mode Constants
- 31
8.2.8 Operator Constants: o
J
Monitor Select: o1
Consta
nt
Name
Set-
Facto-
Change
during
Control Methods
nt
Num-
ber
Display
Description
Set
ting
Range
Facto
ry Set-
ting
g
during
Opera-
tion
Open Loop
Vector
Flux Vector
Page
o1-01
Monitor selection
Set the number of the monitor item to be dis-
played in the earliest 4 monitor items.
(U1-
)
4 to 33
6
B
B
60
o1-01
Monitor Select
(U1-
)
The output monitor voltage (factory setting)
can be changed.
4 to 33
6
B
B
- 60
o1-02
Monitor selection
after power up
Sets the monitor item to be displayed when
the power is turned on.
1: Frequency reference
1 to 4
1
B
B
60
o1-02
Power-On Moni-
tor
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for o1-01
1 to 4
1
B
B
- 60
o1-03
Frequency units
of reference set-
ting and monitor
Sets the units that will be set and dis-
played for the frequency reference and
frequency monitor.
0: 0.01 Hz units
1: 0.01% units (Maximum output fre-
quency is 100%)
2 to 39:r/min units (Sets the motor poles.)
40 to 39999: User desired display
Set the desired values for
setting and display for the
max output frequency
0 to
39999
0
B
B
- 7
- 60
Display Scaling
g
p y
max. output frequency.
Example: When the max. output frequen-
cy value is 200.0, set 12000
Set four digits without the
decimal point
Set the position of the dec-
imal point in the first digit.
39999
- 60
o1-04
Frequency units
of constant set-
ting
Set the V/f pattern setting units. (E1-04, 06,
09 set units)
0: Hz units
1: r/min units
0 1
0
B
- 13
Display Units
1: r/min units
Effective only in the flux vector control
mode.
o1-05
Constant No. dis-
play selection
Set the Operator constant number display
method.
0: Normal display (e.g., A1-00)
0 1
0
A
A
- 60
o1 05
Address Display
0: Normal display (e.g., A1 00)
1: Display MEMOBUS communications
register address
0 1
0
A
A
- 60
8