8.2
Programming Mode Constants
- 21
Setting
value
Page
Control Methods
Function
Setting
value
Page
Flux vector
Open loop
Vector
Function
81
MC answerback (N.C.)
- 68
82
MC answerback (N.O.)
- 68
J
Multi-function Outputs: H2
Constant
Setting
Factory
Change
during
Control Methods
Constant
Number
Name
Display
Setting
Range
Factory
Setting
g
during
Opera-
tion
Open Loop
Vector
Flux Vector
Page
H2-01
Multi-function input
(terminal 9-10)
Terminal 9 Sel
0 to 37
0
B
B
- 42
H2-02
Multi-function input
(terminal 25-27)
Terminal 25 Sel
0 to 37
1
B
B
- 42
H2-03
Multi-function input
(terminal 26-27)
Terminal 26 Sel
0 to 37
2
B
B
- 42
Multi-function Output Functions
Setting
Control Methods
Setting
value
Function
Open loop
Vector
Flux vector
Page
0
During run ON: run command is ON or voltage is being output)
- 43
1
Zero-speed
- 43
2
Frequency agree 1: (Detection width L4-02)
- 54
3
Desired frequency agree 1 (ON: Output frequency =
r
L4-01, detection width in L4-02)
- 54
4
Frequency (Four) detection 1 (ON: +L4-01
output frequency
--L4-01, detection width in
L4-02)
- 54
5
Frequency (Four) detection 2
(ON: Output frequency
+L4-01 or output frequency
%
--L4-01, detection width in L4-02)
- 54
6
Inverter operation ready
READY: After initialization, no faults
7
During DC bus undervoltage (UV) detection
8
During baseblock (ON: during baseblock)
9
Frequency reference selection (ON: Frequency reference from Operator)
A
Run command selection (ON: Run command from Operator)
B
Overtorque detection 1 NO (NO contact: Overtorque detection at ON)
- 56
C
Loss of frequency reference (Effective when operation selection is “1” for L4-05 frequency
reference missing)
- 54
D
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
E
Fault (ON: Faults other than CPF00, CPF01 have occurred.)
NO TAG
F
Not used. (Do not set.)
10
Minor fault (ON: Alarm displayed)
NO TAG
11
Fault reset command active
12
Not used. (Do not set.)
13
Frequency agree 2 (Detection width: L4-04)
- 54
14
Desired frequency agree 2 (ON: Output frequency = L4-03, detection width in L4-04)
- 54
15
Frequency detection 3 (ON: Output frequency
%
--L4-03, detection width in L4-04)
- 54
16
Frequency detection 4 (ON: Output frequency
--L4-03, detection width in L4-04)
- 54
17
Overtorque detection 1 NC (NC Contact: Ttorque detection at OFF)
- 56
18
Overtorque detection 2 NO (NO Contact: Torque detection at ON)
- 56
19
Overtorque detection 2 NC (NC Contact: Torque detection at OFF)
- 56
1A
During reverse run (ON: During reverse run)
1B
During baseblock 2 (OFF: During baseblock)
1C
Motor selection (ON:During moter 1 selection)
1D
Regenerating (ON: Regenerating)
1E
Restart enabled (ON: Restart enabled)
- 56
1F
Motor overload (OL1) pre-alarm (ON: 90% or more of the detection level)
- 43
20
Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)
- 43
30
During torque limit (current limit) (ON: During torque limit)
31
During speed limit. (ON: During speed limit)
- 43
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excita-
tion, operation stop.)
- 43
8