Basic Operation
6.3.1 PG Speed Control Card Settings
- 24
Setting
Function
2
Emergency stop using the emergency-stop time (C1-09).
3
Continue operation (PGO is displayed, and continues operation.)
Overspeed Settings: F1-03, F1-8, F1-09
D
Overspeed refers to an excessive motor speed.
D
Set the conditions (level and time) for detecting overspeed and the stopping method that is used when
an overspeed is detected.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
F1-03
Operation selection at
overspeed
0 to 3
--
1
B
F1-08
Overspeed detection
level
0 to 120
%
115
A
F1-09
Overspeed detection
delay time
0.0 to 2.0
s
0.0
A
D
Settings
Setting
Function
0
Deceleration to stop using deceleration time 1 (C1-02).
1
Coast to stop
2
Emergency stop using the emergency-stop time (C1-09).
3
Continue operation (OS is displayed, and continues operation.)
D
F1-08 and F1-09 Settings
Constant F1-08 sets the overspeed detection level as a percentage of the maximum output frequency.
Constant F1-09 sets the length of time in seconds that the motor speed must exceed the overspeed
detection level in order to generate an overspeed fault.
PG Speed Deviation Settings: F1-04, F1-10, F1-11
D
PG speed deviation refers to the difference between the actual motor speed and the reference speed.
D
These constants set the conditions (level and time) for detecting PG speed deviation and the stopping
method that is used when a PG speed deviation is detected.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
F1-04
Operation selection at
deviation
0 to 3
--
3
B
F1-10
Excessive speed devi-
ation detection level
0 to 50
%
10
A
F1-11
Excessive speed devi-
ation detection delay
time
0.0 to 10.0
s
0.5
A
D
Settings (F1-04)
Setting
Function
0
Deceleration to stop using deceleration time 1 (C1-02).
1
Coast to stop
2
Emergency stop using the emergency-stop time (C1-09).
3
Continue operation (Displays “DEV” and continues control.)
D
F1-10 and F1-11 Settings
Constant F1-10 sets the PG speed deviation detection level as a percentage of the maximum output
frequency. Constant F1-11 sets the length of time in seconds that the difference between the motor
speed and reference speed must exceed the PG speed deviation detection level in order to detect a PG
speed deviation (DEV).
6