Switching voltage, maximum
30 V
Switching current, maximum
27 mA
Contact resistance (on) max.
74 Ω
Contact resistance (off) min.
6 MΩ
Closure time
100 ms
Interval between pulses
100 ms
1.7 Two potential-free pulse outputs (optional)
The potential-free pulse outputs provide counting pulses of the meter.
The pulse outputs close corresponding to the pulse value, see items „pulse value pulse output
1“ and „pulse value pulse output 2“ in display loop “6” (module loop).
Pulse outputs for energy:
The pulse value for energy is always determined by
the last place
of the energy display.
Examples:
Display: 0 kWh
-> pulse value: 1 kWh/pulse
Display: 0,000 MWh
-> pulse value: 0,001 MWh/pulse
Display: 0,000 GJ -> pulse value: 0,001 GJ/pulse
Pulse outputs for volume:
The pulse value for volume is always determined by
the second-to-last place
of the volume display.
Example:
Display: 0,000 m³ -> pulse value: 10 l/pulse (0,01 m³/pulse)
1.7.1 Pin assignments 4-wire cable
Color
Connection
Yellow
IA1
Green
IA1
Brown
IA2
White
IA2
2
Retrofitting with an Additional Communication Interface
During installation of the retrofitting module observe the ESD requirements according to EN 61340-5-1.
This means that on location an antistatic wrist strap with an integrated 1 MΩ resistor has to be used which must be connected
to a proper spot: This is either a grounded pipe or – only with an appropriate adapter! – a Schuko plug grounding socket. The
antistatic wrist strap must be worn tightly on the skin of the wrist.
2.1 Retrofitting PolluTherm F with an additional communication interface
To our calculator further communication interfaces can be added later.
Heat meter
Cooling meter
Heat/cooling meter
Pulse output 1
heat energy
cooling energy
heat energy
Pulse output 2
volume
volume
cooling energy