4
3. Installation
3.1 Installation Preparation
You may need the following tools for the installation:
Screws and nuts, screw driver, Small slotted screw driver, Wire cutter, Ladder, Drill, Saw.
3.1.2 DIP Switch & Jumper settings
Please refer to Appendix I to set the following:
3.1.3 Wiring Diagram
1.
Alarm Input1
2.
Alarm Input2
3.
Alarm Input3
4.
Alarm Input4
5.
Alarm Input5
6.
Alarm Input6
7.
Alarm Input7
8.
Alarm Input Common Port
9.
Alarm Output1
10.
Alarm Output1
11.
Alarm Output2
12.
Alarm Output2
13.
Power - (Black)
14.
Not Used
15.
Power + (Red) 24V AC
16.
Video Output
17.
Video Ground
18.
RS485 +
19.
RS485 -
20.
Not Used
21.
Not Used
22.
Not Used
23.
Not Used
3.1.1 Cables
z
Video Coaxial Cable
The video coaxial cable should be:
1) 75 Ohm impedance.
2) Solid copper wire.
3) 95% braided copper shield.
Check the max transmission distance referring to the chart
below:
INTERNATIONAL GAUGE
TRANSMISSION DISTANCE( MAX.)
RG 59/U
750ft (229m)
RG 6/U
1,000ft (305m)
RG 16/U
1,500ft (457m)
z
RS485 (Data) Cable
0.56mm (24AWG) twisted pair ’s maximum transmission
distances are as follows:
BAUD RATE
TRANSMISSION DISTANCE (MAX.)
2400bps
5,906ft (1800m)
4800bps
3,937ft (1200m)
9600bps
2,625ft (800m)
NOTE: Use RS485 distributor if you need to transmit
further. To learn more about RS485, please refer to
Appendix III.
z
Protocol & Baud rate
z
Dome address
z
Video cable type
z
Alarm output method
z
RS485 termination
resistor
1
2
3
4
5
6
7
8
9
10
11
12
16
17
18
19
20
21
13
14
15
22
23