This page is to set NetAgent SNMP settings so it can be used by a NMS ( Network Management System). (Eg:
SNMPView, SNMPView can be found on the NetAgent Utility CD.)
MIB System
System Name
This section is to give a name to a NetAgent.
System Contact
This section is to give a name to the administrator.
System Location
This section is to set NetAgent location.
Access Control
Manager IP Address
This section is to set the IP address that the administrator can manage NetAgent from. It is valid for up to
8 IP addresses. To manage NetAgent from any IP address, enter *.*.*.* into Manager IP address.
Version
This is to select between SNMPv1& SNMPv2 or SNMPv3 (SNMPv3 only applies to NetAgent 9 series)
Community
This section is to set a Community name for NMS. The community name has to be the same as the set-
ting in NMS.
Permission
This section is to set authorities of administrators. Options are Read, Read/Write, and No Access.
Username/password
When using SNMPv3, username/password must be entered. Password must be at least 8 characters.
Sender and Recipient’s password must match to communicate.
Authentication
This is to select between MD5 and SHA. Length must be at least 8 characters.
Privacy
This is to select DES and AES. Length must be at least 8 characters.
Description
This section is for an administrator to make notes.
Trap Notification
Receiver IP Address
This section is to set IP address for receiving traps sent by NetAgent. It is valid for up to 8 IP Addresses.
Community
This section is to set a Community name for NMS. The community name has to be the same as the set-
ting in NMS.
Trap Type
This section is to select if whether to send trap using PPC MIB or RFC1628
Severity