54
Doc. 20780_03
Planning and Commissioning Manual
ADPRO Passive-Infrared (PIR) PRO Series by Xtralis
NOTE!
Detectors are given IDs (addresses) in the range of 1 to 254. Factory-
set addresses are in the 1 to 10 range. It is recommended to narrow
down the range when searching for a detector so as not to take time
and retrieve the connected detectors more quickly.
Each detector must have a unique address, if more than one detector
is given the same address and connected to the same bus, none of
them will appear on the Software. To resolve this problem, disconnect
all detectors and configure each one separately. This will ensure that
no detector uses the same ID of another one.
3.
Click (Start), or press keys <ALT> + <S>, a list of found detectors appears as shown
below:
The number on the left of the “>” sign is the detector’s ID. The type of the detector and
the firmware version number are on the right of the “>” sign.
You can stop the search process by pressing <ALT> + <S> or clicking (Stop).
To close the search window, click (ESC).
If no detectors are found, the following message appears: