Planning and Commissioning Manual
ADPRO Passive-Infrared (PIR) PRO Series by Xtralis
SW sensitivity
right/left [%]
1
Modifies sensitivity of right/left channel within bandwidth 20
% - 139.39 %.
Reduction of overall sensitivity changes alarm threshold but
leaves coverage of right/left channel unchanged.
SW ATD
ON
Enables “Adaptive Threshold Discrimination”.
OFF Disables
“Adaptive
Threshold Discrimination”.
NOTE!
Disable ATD function prior to walking test
to optimize performance of detector.
When putting “SW Test” to “ON”, ATD
function is disabled automatically in
Software mode.
SW Test
ON
Enabled to perform walking test with Wireless walking tester
CT-PRO.
OFF
Disabled for normal operation.
SW Vandalism
protection/SW
vandal function
ON/
OFF
Enables/ Disables “Anti-Tamper Protection”.
Reset vandal
position
ON
Writes new alignment position into non-volatile RAM as
baseline for anti-tamper protection in case of misalignments.
OFF
Upload of settings to control device happens always
automatically in “OFF”.
- Not
selected.
Relay function
OFF
Disables output function of relay.
ON
Enables output function of relay.
Output function
[Relay |
Transistor]
If relay function is set to “ON”, the following two options are
available in the drop-down menu:
1. “IR + VAN | IR + VAN”: Using relay and transistor open
collector to signal intrusion alarms and tamper alarms.
2. “IR + VAN”: Using only relay to signal intrusion alarms
and using only transistor open collector to signal tamper
alarms. This allows identifying alarms.
Reset alarm
counter
ON
Resets alarm counter to “zero” at next download of settings
to detector.
OFF
No resetting of alarm counter to “zero” at next download of
settings to detector.
Upload of settings to control device happens automatically
in “OFF”.
- Not
selected.
Relay output
logic
Normal
Relay opens when in alarm.
Inverted Relay closes when in alarm.
SW pulse count
2
0 - 10
Number of additional pulses (0 – 10) before an alarm is
generated.
OFF Disables
“Adaptive
Threshold Discrimination”.
NOTE!
Disable ATD function prior to walking test
to optimize performance of detector.
SW Mounting
3
HIGH
Mounting height above than 3 m (10 ft).
LOW
Mounting height less than 3 m (10 ft).
1
Applies only to long-range detector models
2
Applies only to directional detector models
3
Applies only to volume detector models