This BD expansion does not use I/O unit, the converted data is directly sent into PLC register,
also add two extra output points. Extra outputs do not include normal system’s I/O output.
Channels correspond to the PLC register ID:
Channel
Current
Temperature
Set
Temperature
Kp
Ki
Kd
Diff
Start/stop
0CH
ID1000
QD1000
QD1
001
QD1
002
QD1
003
QD1
004
Y1000
1CH
ID1001
QD1005
QD1
006
QD1
007
QD1
008
QD1
009
Y1001
Note:
1. Kp: proportion parameter, Ki: integral parameter, Kd: differential parameter; Diff: control
proportion band.
2.
Control coil’s status (Y1000/Y1001): 0 = means close PID control, 1 = means start PID
control.
3.
Expansion’s input has voltage 0/5V or 0/10V these two modes and filter form to select. Set
via set the 4 channels’ mode, each register has 16 bits. From low bit to high bit, each 4 bits set
one channel’s mode
3-4 Assign input/output ID