This BD board does not use standard I/O units memory addresses, the converted data will be
directly sent into PLC register. The channels correspond to the PLC register ID:
Channel
0CH
1CH
2CH
3CH
AD signal/Temperature
value
ID1000
ID1001
ID1002
ID1003
PID output value
ID1004
ID1005
ID1006
ID1007
Set the target value
QD1000
QD1001
QD1002
QD1003
Kp
QD1004
QD1009
Ki
QD1005
QD1010
Kd
QD1006
QD1011
Diff
QD1007
QD1012
Dead Band
QD1008
-
Start/Stop
Y1000
Y1001
Y1002
Y1003
Note:
1.
PID value:
PID output value:0 to 4095.
2.
Kp:
proportion parameter
3.
Ki:
Integral parameter.
4.
Kd:
Differential parameter.
5.
Diff:
Control proportion band.
6.
Control coil’s status:
Y1000/Y1001 (0 = means stop PID control, 1 = means run PID control
Description:
0CH and 1CH are AD input channels.
2CH and 3CH are PT100 input channels.
Kp:
proportion parameter.
Ki: Integral parameter.
Kd: Differential parameter.
Diff: Control band.
Control Band Diff
: Carry on PID control in the assigned band, beyond the band, don’t carry
on PID control
Start Signal (Y): PID control is closed when Y is 0, open PID control when Y is 1.
Dead Band “Dead Band”: Compare the current PID output value with the preceding PID
output value. If their difference is less than the set Dead Band, the module will abandon the
current PID output value; still transferring the preceding PID output value to PLC main unit.