background image

XP3-BD User Manual 

Page 6 of 30 

MANUL008R2V1 

 

 
 
 
 
 
 

      

 

Item 

Voltage Input 

Temperature Input 

Analogue Input 
Signal 

DC: 0 to 5V, 0 to 10V 
(Input resistor 300kΩ) 

Platinum Resistor PT100  
(2-wire format) 

Temperature 
Testing   band  

-100 to 350 degrees C 

Resolution 

0.15mV 10/16383 

0.1 

Digital  Output   
band  

0 to 16383 

-1000 to 3500 

Integrate 
Precision 

±0.8% of full scale 

Convert Time 

15ms × 4 channels 

PID 

Output 

Value 

0 to K4095 

Vacant 
Defaulted 
Value 

3500 

    Input 
Specialty 

 

 

Isolation 

No isolation between each channel of PLC 

 Used points 

0 point (As operated via data register, so the used points are not limited 
by PLC’s max control points)  

 

 
 
 
 
 
 
 
 
 
 
 
 

 

2-2 Specs 

Содержание XP3-BD series

Страница 1: ......

Страница 2: ...0 2 7 Application of PID output value 10 2 8 Programs 11 Chapter 3 K type thermo coupling temperature PID board XP3 2TC P 3D 3 1 General 13 3 2 Specs 14 3 3 External installations and connections 15 3...

Страница 3: ...ly on the main unit 2 Then connect the model online via XCP edit tool in the Window menu choose Config BD Board C Image 1 3 Click it in the Config BD Board C dialog box choose Other BD Just as shown i...

Страница 4: ...UL008R2V1 2 AI and temperature sampling board XP3 2AD2PT BD 2 2 Specs 2 3 External installations and connections 2 1 General 2 5 Working Mode settings 2 6 Control settings 2 4 Assignment of input ID 2...

Страница 5: ...5 of 30 MANUL008R2V1 2 1 General 14 bits high precision analogue input 2 Channel voltage 0 10V 0 5V selectable analogue input 2 channels PT temperature testing resistor PT100 two wire format temperatu...

Страница 6: ...0 to 350 degrees C Resolution 0 15mV 10 16383 0 1 Digital Output band 0 to 16383 1000 to 3500 Integrate Precision 0 8 of full scale Convert Time 15ms 4 channels PID Output Value 0 to K4095 Vacant Defa...

Страница 7: ...tallation of Board Open the board s cover at the back of XP3 As shown in the following image install it according to the pin arrangement Then fix it with screws close the cover 2 Connection See the fo...

Страница 8: ...rameter 4 Kd Differential parameter 5 Diff Control proportion band 6 Control coil s status Y1000 Y1001 0 means stop PID control 1 means run PID control Description 0CH and 1CH are AD input channels 2C...

Страница 9: ...decrease system s shake 5 Temperature control proportion band means in the assigned band carry on PID control beyond the band do not carry on PID control CH1 CH 0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 B...

Страница 10: ...and Means in the assigned band to carry out PID control PID Temperature Control Curve is Shown Below Note Each parameter s reference value Kp 20 100 Ki 5 20 Kd 200 500 DIFF 100 200 This reference valu...

Страница 11: ...800 QD1000 MOV ID1000 D10 M8000 END MOV K30 QD1004 MOV K5 QD1005 MOV K500 QD1006 MOV K150 QD1007 MOV K200 QD1008 MOV ID1004 D1000 Y1000 M8 2 8 Programs Write CH0 s input value into D10 Set CH0 s value...

Страница 12: ...000 T200 K200 T200 T200 D1200 Y3 Y1000 M10 END MOV K30 QD1009 MOV K5 QD1010 MOV K500 QD1011 MOV K150 QD1012 D1100 K0 T200 is 10ms timer Convert PID output value 0 4095 to be value of 0 200 Via ON OFF...

Страница 13: ...cs 3 3 External installations and connections 3 4 Assign input output ID 3 5 Working Mode settings 3 6 Control speciality 3 7 Programs 3 1 General Analogue input used by thermocouple K type temperatur...

Страница 14: ...nts Temperature Testing Band 0 to 970 C Digital Output Band 0 9700 16 bits binary Output Points 2 points Output Format NPN collector open circuit transistor output Control Precision 0 4 C Resolution 0...

Страница 15: ...tall Position of Expansion Board Installation Method of Expand Board 1 Open the expansion cover behind XP3 See the following diagram then install according to the pin and fix with screws 2 Connection...

Страница 16: ...it and output transistor use optical coupling device to insulate Each public module is divided separately Response time The time from PLC drive optical coupling device to transistor ON OFF is not more...

Страница 17: ...0CH ID1000 QD1000 QD1 001 QD1 002 QD1 003 QD1 004 Y1000 1CH ID1001 QD1005 QD1 006 QD1 007 QD1 008 QD1 009 Y1001 Note 1 Kp proportion parameter Ki integral parameter Kd differential parameter Diff cont...

Страница 18: ...PID output value this period is called Temperature Control Cycle CH1 CH0 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 0 2 Sec 0 2 Sec 1 20 Sec 1 20 Sec FD8306 H O O O O 0CH 1CH 3 5 Working Mode settings 1...

Страница 19: ...control 2 Temperature Control Cycle When carrying out PID adjustment the output will carry on heating according to the duty cycle got by PID output value this period is called Temperature Control Cyc...

Страница 20: ...MOV QD1000 K500 MOV QD1003 K5 MOV QD1002 K30 MOV QD1001 M8000 END K150 MOV QD1004 Y1000 M0 3 7 Programs Set value in CH0 as 800 80 degrees Set CH0 s Kp as 30 Start stop CH0 Set CH0 s Ki as 5 Set CH0...

Страница 21: ...30 MANUL008R2V1 4 Analogue AI AO temperature sampling board XP3 2PT2ADIDA BD 4 1 General 4 2 Specs 4 3 External installations and connections 4 4 Assignment of input ID 4 5 Working Mode settings 4 6...

Страница 22: ...R2V1 4 1 General 14 bits high precision analog input 10 bits high precision analog output 2 channels voltage 0 10V or 0 5V selectable analog input 2 channels PT temperature testing resistor PT100 2 wi...

Страница 23: ...mA Temperature Testing band 100 to 350 C Distinguish Ratio 0 15mV 10 16383 0 1 C 1 1023 Digital Output band 0 to 16383 1000 to 3500 Integrate Precision 0 8 of the full scale Conversion Time 15ms 4 cha...

Страница 24: ...raph and then install it according to the pin arrangement Then fix it with screws close the cover 2 Connection format As shown in the following graph Note Module s 0 20mA or 4 20mA output needs 24V po...

Страница 25: ...1008 QD1012 Dead Band QD1013 Start Stop Y1000 Y1001 Y1002 Y1003 Note 1 Both 0CH and 1CH are PT input channels 2CH and 3CH are AD input channels 2 Kp proportion parameter 3 Ki Integral parameter 4 Kd D...

Страница 26: ...14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4 filter 0 0 10V 1 0 5V 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4 filter 0 0 10V 1 0 5V 4 5 Working mode sett...

Страница 27: ...l parameter Temperature control proportion band in the assigned band and will carry on PID control D A channel Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 00 1 2 filter 01 not filter 10 1 3 filter 11 1 4...

Страница 28: ...control 2 Temperature Control Cycle When carrying out PID adjustment the output will carry on heating according to the duty cycle got by PID output value this period is called Temperature Control Cyc...

Страница 29: ...Programs Write channel 0 input temperature into D0 Write channel 1 output temperature into D2 Treat CH2 Pressure setting 0 10V as the set value in CH3 Write CH3 Pressure Feedback into D4 Set AD Channe...

Страница 30: ...EMARK OF XINJE ELECTRICAL CO LTD REPLICATION OF THE INFORMATION CONTAINED WITHIN THIS DOCUMENT WITHOUT PRIOR NOTIFICATION AND AGREEMENT IS PROHIBITED Engineered and supplied by International partners...

Отзывы: