39
6. Output specification and wiring
6-1. Output specification
(1) transistor output
External power supply
Below DC5~30V
Circuit insulation
Optocoupler insulation
Action indicator
LED light
Max load Resistive
load
0.3A
inductive
load
7.2W/DC24V
Light load
1.5W/DC24V
Min load
DC5V 2mA
Open circuit leakage
current
< 0.1mA
Response
time
OFF→ON
< 0.2ms
ON→OFF
< 0.2ms
(2
) High speed pulse output
Model
T4
High speed pulse output terminal
Y0~Y3
External power supply
Below DC5~30V
Action indicator
LED light
Max current
50mA
Pulse max output frequency
100KHz
Note:
(1) When the high-speed pulse output function is used, the PLC can output pulses up to 200kHz, but it can not
ensure that all servos operate normally. Please connect a resistance of about 500 ohms between the output and
the 24V power supply.
(2) The PLC is generally equipped with a plug-in spring connector to facilitate wiring when it leaves the factory.
The connector requires that the stripped length of the wire shall be at least 1.5cm. When wiring, press the
yellow spring switch with a small screw drive, insert the wire into the corresponding socket, and release the
spring switch.
6-2
.
Transistor output
Transistor (NPN) output types can be divided into high-speed pulse output and ordinary transistor
(1)
Normal transistor output
External Power Supply
Please use DC5~30V power supply to drive the load.
Circuit Isolation