commissioning and operation.
Measurement in 480Vac
Measurement points on live side
Unit
Nominal value
Specified range
L1 to N
Voltage
277 V
± 10%
L2 to N
Voltage
277 V
± 10%
L3 to N
Voltage
277 V
± 10%
L1 to L2
Voltage
480 V
± 10%
L1 to L3
Voltage
480 V
± 10%
L2 to L3
Voltage
480 V
± 10%
N to PE (on connection terminal)
Voltage
0 V
PE to N (on connection terminal)
Resistance
<1000m
Ω
in
TN-S system
variable according
local law/standards
and different
earthing system
Table 4.7.1
Measurement in 208Vac
Measurement points on live side
Unit
Nominal value
Specified range
L1 to N
Voltage
120 V
± 10%
L2 to N
Voltage
120 V
± 10%
L3 to N
Voltage
120 V
± 10%
L1 to L2
Voltage
208 V
± 10%
L1 to L3
Voltage
208 V
± 10%
L2 to L3
Voltage
208 V
± 10%
N to PE (on connection terminal)
Voltage
0 V
PE to N (on connection terminal)
Resistance
<1000m
Ω
in
TN-S system
variable according
local law/standards
and different
earthing system
Table 4.7.2