Using the System Settings Menu
975-0298-01-01
3–13
System Settings Menu Configuration Items
Menu item
Description
Values/Action
Default
Invert
Enables or disables inverting for all inverters
in the system. Press Enter to view and select
values.
Enabled, Disabled
Enabled
AC Charge
Enables or disables charging on AC input for
all inverter/chargers in the system. Press
Enter to view and select values. This
command does not affect Solar Charge
Controllers.
Enabled, Disabled
Enabled
System Mode
Places all the devices in the system in the
selected mode. Press Enter to view and select
values. See “System Modes” on page 4–2.
Operating, Standby
Operating
Cascading
Enables or disables cascading parameters
when configuring device settings. See
“Using Cascading Parameters” on page 3–
14.
Enabled, Disabled
Disabled
Connection
Names
Customizes the names of AC and DC
connections in the system. For example,
“AC1” can be changed to “Grid Power.”
House Battery, Start
Battery, Solar Array,
Grid, Generator, AC Load
n/a
View Fault
List
Displays the Fault List screen, which shows
active faults in the system (up to 20). See
page 4–9.
Press Enter to view list.
n/a
View Warning
List
Displays the Warning List screen, which
shows active warnings in the system (up to
20). See page 4–5.
Press Enter to view list.
n/a
Clear All Flts/
Wrns
Clears active faults and warnings on all
devices on the system.
Press Enter to clear faults
and warnings
n/a
View Device
Info
Shows the model number, firmware serial
number and firmware revision for each
Xanbus-enabled device.
Press Down arrow to
view information for each
device.
n/a
Содержание XW-SCP 865-1050
Страница 1: ...XW System Control Panel Owner s Guide Fault Warning System Control Panel II Standby ...
Страница 2: ......
Страница 3: ...XW System Control Panel Owner s Guide ...
Страница 30: ...2 16 ...
Страница 46: ...3 16 ...
Страница 56: ...4 10 ...
Страница 62: ...5 6 ...
Страница 66: ...A 4 ...
Страница 72: ...WA 6 ...
Страница 75: ......