Designing Your Installation
445-0145-01-01
3–9
Calculating Size of Chassis Ground Cable for
XPower 1750 Plus
Refer to
Table 3-4
to plan the size of the chassis ground cable that runs
from the DC grounding point to the chassis ground screw on the inverter’s
DC panel.
Table 3-3
Recommended DC Input Wire Sizes & Lengths:
XPower 1750 Plus
RV
a
(Recreational Vehicle)
a. Based on US National Electrical Code NFPA70, Article 551 and Table 310-17, 90C
cables located outside of engine spaces.
Cable length:
Battery to Inverter (one way)
Minimum Cable Size
Maximum Battery Fuse
Size
6 feet (1.8 m) or less
No. 1/0 AWG
250 Adc
Note: Never use a cable longer than 6 feet (1.8 m) with the
XPower 1750 Plus
.
Appropriate size cable can be bought at a welding supply house.
Table 3-4
Recommended Chassis Ground Cable sizes:
XPower 1750 Plus
Application
Chassis ground cable size
(Stranded cable is recommended)
Recreational Vehicle
a
a. Based on US National Electrical Code NFPA70, Article 551, par. 551-20c.
No. 8 AWG
Note: There are no restrictions on length for the chassis ground cable.
XPower 1200 Plus 1750 Plus.book Page 9 Friday, October 21, 2005 4:19 PM