Wiring the Inverter
3–12
975-0466-01-01
Network Components
Terminators
Network terminators (Figure 3-9) are required at both ends of the network to
ensure the communication signal quality on the network. Network terminators are
inserted into a GT Inverter RJ45 (Xanbus) port. The GT Inverter comes with one
network terminator pre-installed.
GT Inverter Xanbus
ports
Two RJ45 ports are provided on the GT Inverter for making network connections.
See Figure 3-10 for the location of these ports.
CAUTION: Unpredictable network operation
Do not exceed the maximum total Xanbus network length shown in Table 3-2, “Total
Xanbus Network Length” on page 3–11. Proper network operation cannot be guaranteed
when these distances are exceeded.
Important:
When creating long Xanbus networks (i.e. greater than 100 m), you must
verify network integrity using a CANbus network analysis tool such as the Maretron
N2KMeter Diagnostic Tool for NMEA2000 compatible networks. See “Verifying the
Xanbus Network” on page 3–15.
Figure 3-9
Network Terminator
Figure 3-10
Location of Xanbus RJ45 Ports
RJ11 ports
(not used)
Xanbus
RJ45 ports
RS-232 port (used to connect a PC to
use GT-View. See page 3–16.)
Содержание GT2.8-AU-QC-230
Страница 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT2 8 AU QC 230 GT5 0 AU QC 230 ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 14: ...Contents xii 975 0466 01 01 ...
Страница 16: ...xiv ...
Страница 18: ...xvi ...
Страница 58: ...4 4 ...
Страница 70: ...Monitoring the Inverter 5 12 975 0466 01 01 ...
Страница 76: ...Maintenance and Troubleshooting 6 6 975 0466 01 01 ...
Страница 82: ...A 6 ...
Страница 89: ......