Wiring the Inverter
3–14
975-0466-01-01
•
Allow separation between data and power cables (data cables should only
cross a power cable at right angles).
•
Do not staple the cable with metal cable staples. Use the appropriate hardware
fasteners to avoid damage to the cable.
Connecting Network Cable between Inverters
This procedure assumes only two inverters are installed. However, there can be up
to ten inverters wired in this configuration.
To provide communication between multiple inverters:
1. Remove the communication ports covers from all inverters. See Figure 3-12.
1. Connect the network cable to an empty RJ45 port in Inverter #1.
2. Pass the cable through the cable clamp on the communication ports cover of
Inverter #1.
3. Pass the cable between Inverter #1 and Inverter #2, securing the cable
appropriately.
4. Pass the cable through the cable clamp on the communication ports cover of
Inverter #2.
5. Connect the network cable to an empty RJ45 port in Inverter #2.
6. For more than two inverters, continue connecting cable as described above.
7. If not already installed, insert male network terminators into the empty RJ45
ports in the inverters at the beginning and end of the network.
After connecting network cables and inserting terminators, there should be no
empty RJ45 ports in any connected inverter.
CAUTION: Unpredictable device behavior
Do not connect one end of the network to the other to make a ring or loop.
Содержание GT2.8-AU-QC-230
Страница 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT2 8 AU QC 230 GT5 0 AU QC 230 ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 14: ...Contents xii 975 0466 01 01 ...
Страница 16: ...xiv ...
Страница 18: ...xvi ...
Страница 58: ...4 4 ...
Страница 70: ...Monitoring the Inverter 5 12 975 0466 01 01 ...
Страница 76: ...Maintenance and Troubleshooting 6 6 975 0466 01 01 ...
Страница 82: ...A 6 ...
Страница 89: ......