Configuration
91
Selection make contact (close) / break contact (open)
In the submenu CONF REL O/C the function of a relay as make contact or break contact is laid
down.
Setting:
Submenu "CONF REL O/C“.
With
enter submenu
" CONF REL O/C ".
Relay 1 is closed in an active condition.
With
select between
CLOSE or
OPEN.
With
accept and go on to
setting of relay 2.
The relays 2 to 4 can be configured in the same way as make contacts or break contacts.
Exception: If a relay is assigned to the POWER FAIL function it always works as a break
contact. (With power failure, all relays are open!)
After the function for the last relay has been set the program goes back to the beginning of the
configuration menu; the display shows CONFIG.