TReX User Manual v15.30 Firmware
Alert-Based Cooling System
In this example, a TReX-460 is set up in a hot environment with a cooling fan controlled from
Digital Output 4
. The intended behaviour is that the TReX will turn on the cooling fan for 10
minutes whenever it’s onboard temperature sensor passes 90
°C
.
PLC Configuration:
*PLC_RUNG=01:[Q:8]-------[-]---------[-]---------(T:1)
*PLC_RUNG=02:[TT1]---+ [-] [-]
*PLC_RUNG=03:[TT1]-------[-]---------[-]---------(Q:4)
*PLC_RUNG=04:
*PLC_RUNG=05:
*PLC_RUNG=06:
This PLC program requires the configuration of the
Temperature Alert
, the
Alert Output
and
the
Overtemp
. The first two configuration items can be found in the
ALERTS
sub-menu of
the main configuration menu and the third can be found in the
SYSTEM
submenu of the main
configuration menu.
© WTE Limited, 2022 – Christchurch New Zealand
Page 187 of 302
Содержание TReX-460
Страница 87: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 87 of 302...
Страница 193: ...TReX User Manual v15 30 Firmware output of FAILED CR WTE Limited 2022 Christchurch New Zealand Page 193 of 302...
Страница 280: ...TReX User Manual v15 30 Firmware SIDE Mount WTE Limited 2022 Christchurch New Zealand Page 280 of 302...
Страница 281: ...TReX User Manual v15 30 Firmware Bottom Mount WTE Limited 2022 Christchurch New Zealand Page 281 of 302...
Страница 286: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 286 of 302...
Страница 302: ...TReX User Manual v15 30 Firmware WTE Limited 2022 Christchurch New Zealand Page 302 of 302...