TReX User Manual v15.30 Firmware
Latched Motor Starter
A TReX-460 is set up with a
normally open start button
connected to
Digital Input 1
and a
normally closed stop button
connected to
Digital Input 2
.
Digital Output 1
of the TReX is
configured to control a pump motor (through external relay or contactor). The intended
behaviour is that the motor will start when the start button is pressed and will only stop when
the stop button is pressed, disconnected or damaged. This can be achieved with the following
configuration:
After pressing the start button,
Output 1
is held closed until
Input 2
is opened by pressing the
stop button.
PLC Configuration:
*PLC_RUNG=01:[I:1]-------[I:2]-------[-]---------(Q:1)
*PLC_RUNG=02:[Q:1]---+ [-] [-]
*PLC_RUNG=03:
*PLC_RUNG=04:
*PLC_RUNG=05:
*PLC_RUNG=06:
© WTE Limited, 2022 – Christchurch New Zealand
Page 181 of 302