TReX User Manual v15.30 Firmware
“Pump Station 1” Configuration
“Pump Station 2” Configuration
The MASTER unit has configured REMOTES to a value of 2 (meaning there are 2 SLAVE
units). Note that first SLAVE ID must be set to a value one higher than the MASTER ID, and
each SLAVE in the system must be consecutively numbered.
The SLAVE configuration is unique in that both the LOCAL ID and REMOTE ID need to be
the same. In this configuration, the MASTER unit requires these settings in order to identify
the SLAVE unit messages.
The SCADA application will report inputs 1-8 to be from “Remote Station”, inputs 9-16 from
“Pump Station 1” and inputs 17-24 from “Pump Station 2”.
See
Modbus Protocol
for more information.
© WTE Limited, 2022 – Christchurch New Zealand
Page 213 of 302