Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Operation
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
51
of
69
5.5.1 AC Voltage
Requirements for measuring the AC voltage externally:
•
The motor protecting switch (-F31) must be in position
I
Procedure:
1.
Ensure
that the measuring device is connected (Section 3.5.2.5).
2.
Start
the product (Section 5.4).
3.
Check
if the values are within the specified limits (Table 10).
5.5.2 AC Current
Procedure:
1.
Ensure
that the measuring device is connected (Section 3.5.2.6).
2.
Start
the product (Section 5.4).
NOTICE: The internal current sensors (Figure 7) have a translation ratio of 800/1A.
3.
Check
if the values of the AC current are within the specified limits (Table 10).
5.5.3 Ambient Temperature
The product offers the possibility to show the ambient temperature on the customer
interface.
Procedure:
1.
Ensure
that the temperature sensor is connected (Section 3.5.2.7).
2.
Start
the product (Section 5.4).
3.
Check
if the values are within the limits of the specified limits (Table 11).
5.6
Stopping the Product
Procedure:
1.
Set
the product in operation mode
OFF
via the user interface.
2.
Switch
the AC circuit breaker in position
OFF
. The DC circuit breaker is
operated automatically.