LEMCOM EtherNet/IP™ - User manual
EtherNet/IP™
COVAL - LMEIP-UK-D-1155UM0067
20/42
RSLinx
– Check LEMCOM visibility
Use RSLinx Classic to check whether the LEMCOM
’s IP address set is detected by the controller.
1. Start RSLinx Classic (Start menu > Rockwell Software > RSLinx > RSLinx Classic)
2. Click on the RSWho button:
3. Then open the path
AB_ETHIP1, Ethernet
(EtherNet/IP driver must be configured in
Communicat
ions > Configure drivers… menu). The LEMCOM can be seen with their IP
addresses:
Add LEMCOM module to an RSLogix 5000 project
Follow the steps below to add a LEMCOM module (or a LEMCOM island) to a project in RSLogix
5000.
1. In section
I/O configuration
, right-click on
Ethernet
then “New module…”
2.
Type in “Lemcom” or “Coval” in the search box. Select the item that appears in the list then
click on “Create” (note that
LEMCOM EDS file must be installed
prior to this).
Содержание Greenstar 36LXi
Страница 6: ...LEMCOM EtherNet IP User manual LEMCOM overview COVAL LMEIP UK D 1155UM0067 6 42 LEMCOM OVERVIEW...
Страница 7: ...LEMCOM EtherNet IP User manual LEMCOM overview COVAL LMEIP UK D 1155UM0067 7 42...
Страница 8: ...LEMCOM EtherNet IP User manual LEMCOM overview COVAL LMEIP UK D 1155UM0067 8 42...