Manual WIP1 GB
Woodward
DOK-TD-WIP1 Rev.F
39
6.6.8 Setting of parity
>>Parity_Check<<
_____even_______
The following three parity settings are possible:
even parity
odd parity
no parity
The setting can be changed by push buttons <+> and <-> and saved by pressing <ENTER>.
6.6.9 Indication of the software version
In this point of the menu, the number of the relay soft-ware version can be called up. When receiving the re-
lay description it always should be checked whether the description really applies for the actual relay soft-
ware version (a respective note can be found in the index).
Software_Version
V02-1.00________
6.7 Tripping method/Relay matrix
6.7.1 Reset
Here we have to distinguish whether the LED and the bistable relay 1 are to be reset automatically or manu-
ally. Refer to Chapter 6.9
>>>>>>RESET<<<<<
Manuell_________
Automatisch_____
6.7.2 Tripping method
This is to determine whether the C.B. is activated direct via the electric pulse output or if to be switched via
an interposing C.T. circuit (see figure 3.2 and 3.3 and 3.5).
Kind_of_Tripping
Electro_Pulse___
Note:
If parameter is set on electric-pulse the output relay will also operate in case of tripping.
If parameter is set on relay the electric impulse output doesn’t connect with a trip coil.