Setting list WIP1
Note !
All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protect-
ed.
Project:
Woodward job.-no.:
Function group: =
Location: +
Relay code: -
Relay
functions:
Password:
Date:
System parameters
Parameter
Unit
Default
setting
Actual
setting
WIP11 WIP12
WIP13
Language
English
X
X
X
Password
++++
X
X
X
Date setting*
01.01.1990
X
X
X
Time setting*
00:00:00
X
X
X
Rated frequency
Hz
50
X
X
X
Slave address
1
X
Baud rate**
9600
X
Setting the parity**
even
X
* Actual setting at delivery ** Modbus protocol only
Protection parameters
Parameter
Unit Default
setting
Actual
setting
WIP
11
WIP
12
WIP
13
Overcurrent pickup value
A
0.5
X
X
X
Selection of tripping characteristic
(phase current element)
Definite
Time
X
X
X
Overcurrent trip delay
s
0.06
X
X
X
Reset-Mode for inverse time tripping character-
istics
s 0 X
X
X
Minimum tripping time (phase current element)
s
0.06
X
X
X
High set overcurrent value
A
1.0
X
X
X
Time delay for high set overcurrent
s
0.06
X
X
X
Earth fault current pickup value
A
0.05
X
X
X
Selection of characteristic (earth fault element)
Definite
Time
X
X
X
Trip delay for earth fault current
s
0.06
X
X
X
Reset mode for inverse time tripping
characteristics
s 0 X
X
X
Minimum tripping time (earth fault element)
s
0.05
X
X
X
Pickup value of earth fault high set element
A
0.1
X
X
X
Time delay for earth fault high set element
s
0.06
X
X
X