2. General
The WIP1 is a self powered time overcurrent relay with multi-characteristics. Definite time and inverse time
trip-ping characteristics can be selected. The WIP1-1 does not require any aux. voltage supply, consequently
it can also be used for switchboards without built-in batteries. It takes its power supply energy from the C.T.
circuits and provides the tripping pulse energy to the circuit breaker. Due to its wide setting ranges, the trip-
ping characteristic can be selected to protect a wide variety of different equipment.
The WIP1 is available with earth fault element . The relay is buffered by a battery for feeding the LC display
as well as for memorizing fault values and reset of the trip relay. Failure of the battery has no effect on the
protective functions of the relay. The battery has a service life of more than 10 years.