9.2 Setting ranges and steps
Setting range
Step
Tolerance
I>
WIP1-1
0.5...2.5 A (EXIT)
WIP1-2/WIP1-3
0.2...2.5 A (EXIT)
0.01; 0.02; 0.05; 0.005; 0.01;
0.02; 0.05;
±5% of setting value
±5% of setting value
t
I>
0.06 - 300 s
(definite time)
0.05 -10
(inverse time)
0.01; 0.02; 0.1; 0.2; 0.5; 1.0;
2.0; 5.0; 10; 20 s 0.01; 0.02;
0.05; 0.1; 0.2; 0.5
±3% or ±10 ms
±5% for normal inverse
±7.5% for very and
extremely inverse and
X^2 - X^4
tmin
0,06... 2 s
0.01 s; 0.02 s; 0.05 s
±3% or ±20 ms*
I>>
1... 35 A (EXIT)
0.02; 0.05; 0.1; 0.2; 0.5; 1.0 A ±3% of setting value or min.
±1% In
t
I>>
0.06... 2 s
0.01 s; 0.02 s; 0.05 s
±3% or ±10 ms
Table 9.1: Setting ranges phase current element
* Currents in the range from 0.5 to 1.5 A lead to trippings with increased trip delays (up to 50 ms).
If a C.T. current >0.5 A was present before tripping, the trip delay decreases (about 20 ms).
Setting range
Step
Tolerance
IE>
0.05...2.0 A (EXIT)
0.001; 0.002; 0.005; 0.01;
0,02
±3% of setting value or
min. ±1% In
t
IE>
0.06 - 300 s
(definite time)
0.05 -10
(inverse time)
0.01; 0.02; 0.1; 0.2; 0.5; 1.0;
2.0; 5.0; 10; 20 s
0.01; 0.02; 0.05; 0.1; 0.2; 0.5
±3% or ±20 ms
±5% for normal inverse
±7,5% for very and
extremely inverse
tmin
0.05... 2 s
0.01 s; 0.02 s; 0.05 s
±3% or ±10 ms
IE>>
0.1... 9 A (EXIT)
0.02; 0.05; 0.1; 0.2; 0.5 A
±3% of setting value or
min. ±1% In
t
IE>>
0.06... 2 s
0.01 s; 0.02 s; 0.05 s
±3% or ±10 ms
Table 9.2: Setting ranges earth current element
Annotation to WIP1-1:
The earth fault current element is only activated if the current flowing in at least one of the phases is higher
than the lowest adjustable threshold of the phase overcurrent element (0,5 A).
Technical data subject to change without notice!