7.2.3 Checking the tripping circuits
Parameter <SIGNAL INPUT BLOCKING> is followed by
>>>>>RELAY-<<<<<
>>>>>TEST<<<<<<<
This mode can only be entered in battery operation, i.e. when there is no current flowing.
By pressing push button <SELECT/RESET> the test mode is entered and the password queried.
>>>Relay_Test<<<
_Password:_xxxx_
Pre-condition for entering the relay test mode is that the test current has been applied within 30 s. If the time
has elapsed, the program returns to the standard mode and the display shows:
>>>PROTECTION<<<
>>>>SETTINGS<<<<
After entering the correct password, the trip mode starts upon the following inputs.
>>TEST_CURRENT<<
>>SET_TO_>1Amp<<
When 1 A is reached, test of the relay begins. The protection function is blocked through the test procedure
because exceeding of the set threshold would result in tripping. The display shows:
>>>Relay_Test<<<
>>>is_running<<<
In the following the test procedure is described in de-tail.
Test: Electro pulse output
Test: Alarm relay
Test: Flag indicators
These outputs are controlled for 150 ms and since they are controlled by a common processor signal, they
can only be tested together. The alarm relay remains energized.
Break of 1s
Self-test relay energizes for 1s
Break of 1s