9.2.5.8—Unshielded Discrete I/O
I/O Module in Cabinet
Use Shielded cable from MicroNet module to I/O module (FTM, etc.)
Ground cable direct at MicroNet module and I/O module
Locate as close to I/O cable entry point as possible;
Locate I/O module away from sensitive analog areas (> 6”);
I/O Cable w/ I/O Module in Cabinet
Route I/O cable against cabinet metal wall from entry point to I/O module;
Do not let other cables within 12” of unshielded discrete I/O cables if they
are parallel for > 2’
Do not let other cables within 6” of unshielded discrete I/O cables if they are
parallel for less than 2’
Limit length of unshielded I/O cable inside the cabinet. Any length over 2’ is
too long
If lengths greater than 2’ are required, special considerations should be
used to separate this unshielded wiring from other circuits and minimize
electromagnetic and RF emissions.
I/O Module not in Cabinet
Route cable from MicroNet module to I/O module with cable against cabinet
metal wall
Ground “MicroNet module to I/O module” cable at entry point to cabinet and
to I/O module
9.2.6—Third Party Hardware
CE Compliant to Light Industrial Levels
Locate inside the cabinet, away from all I/O cables that enter or exit the
cabinet by >12”
Locate from all other cables > 6” away
Use only CE compliant devices
CE Complaint to Industrial Levels
Locate based on Zoning restrictions
9.2.7—Ethernet I/O Connections
Use Shielded Twisted Pair (STP) category 5 Ethernet cable
Route Ethernet cable away from all other Internal cabling and external I/O
cabling
Ground internal Ethernet cable at the CPU card and at the entry point to the
cabinet
9.2.8—CAN I/O Connections
A shielded CAN cable as defined in section 5.1.9 of volume 1 of this
manual.
Route the CAN cable away from all other Internal cabling and external I/O
cabling.
Ground the internal CAN cable shield at the entry point to the cabinet.
AC couple the CAN cable shield to earth at each of the CAN devices
external to the MicroNet cabinet.
AC couple the CAN cable shield to earth at each of the CAN devices
internal to the MicroNet cabinet.
Содержание Vertex-Pro
Страница 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Страница 72: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 62 Woodward Figure 8 2 24 8 Analog FTM Schematic ...
Страница 74: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 64 Woodward Figure 8 4 Analog Combo FTM Schematic ...
Страница 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Страница 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Страница 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Страница 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Страница 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Страница 111: ......