Manual 26489V1
Vertex-Pro Motor-Driven Compressor Control
Woodward
7
2.4.4—Simplex Inputs and Outputs
Each I/O module has connectors on the faceplate. For analog and discrete I/O,
cables connect the module to a Field Terminal module (FTM). The FTM is used to
connect to the field wiring. For communications on the CPU, FTMs are not used.
Cables are connected directly to the faceplate of the communications on the CPU.
The following diagram shows the flow of analog and discrete inputs from the field
to the application.
Figure 2-4—Input Flow
Figure 2-5—Output Flow
2.4.5—Redundant Inputs
One level of redundancy is available. This involves wiring two external input
devices to two separate input channels. See Figure 2-7. In the event of a failed
sensor or a failure in the connection from the sensor to the control, a valid input is
still available
Figure 2-6—Redundant Sensors
The second level is wiring two external input devices to two separate I/O modules.
See Figure 2-8. In the event of a failure in one of the sensors, connections, cables,
FTMs, or I/ O modules, a valid input is still available.
Содержание Vertex-Pro
Страница 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Страница 72: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 62 Woodward Figure 8 2 24 8 Analog FTM Schematic ...
Страница 74: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 64 Woodward Figure 8 4 Analog Combo FTM Schematic ...
Страница 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Страница 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Страница 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Страница 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Страница 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Страница 111: ......